5.5 Perform the basic setup
5.5.1 Set the engineering units
Procedure
1. Under Menu
, select Parameter Basic Setup.
2. In the Engineering Units list, select Metric or Imperial.
Option Description
Metric Length: m
Temperature: °C
Volume flow: m
3
/h
Imperial Length: in.
Temperature: °F
Volume flow: US gal/h
3. Select Write to device.
5.5.2 Enter the reference height
Procedure
1.
Under Menu
, select Parameter Basic Setup.
2. Enter the Reference Height.
3. Select Write to device.
Related information
Reference height
5.5.3 Configure the analog output
The transmitter can be set to output the level or volume flow as a 4-20 mA signal.
Procedure
1. Under Menu
, select Parameter OUT2 Analog Output.
2. In the OUT2 Configuration list, select Analog Output 4-20 mA.
3. In the Analog Control Variable list, select Level or Volume Flow.
4. In the Alarm Mode list, select Low Alarm or High Alarm.
5. Select Analog Range Values, and then enter the desired Upper Range Value (20
mA) and Lower Range Value (4 mA).
6. Select Write to device.