C.2 Basic setup
C.2.1 Engineering units
Sets the unit of measure for length, temperature, and volume flow.
Option Length unit Temperature unit Volume flow unit
Metric m °C m
3
/h
Imperial inch °F US gal/h
After appropriate units have been selected, all configuration parameters and transmitter
variables will be expressed in these units.
C.2.2 Reference height
Distance between the Device Reference Point and Zero Level.
Figure C-2: Reference Height
A
B
C
D
A
B
C
A. Device Reference Point
B. Reference Height
C. Zero Level
D.
0.6 in. (15 mm)
Ensure the Reference Height is set as accurate as possible. The transmitter measures the
distance to the product surface and subtracts this value from the Reference Height to
determine the level.
Configuration parameters Reference Manual
May 2021 00809-0200-4480
80 Rosemount 1408A Level and Flow Transmitter