Reference Manual
Table Of Contents
- Rosemount 1408H Level Transmitter
- Contents
- 1 Introduction
- 2 Transmitter overview
- 3 Mechanical installation
- 3.1 Safety messages
- 3.2 Installation considerations
- 3.3 Mounting preparations
- 3.4 Mount transmitter on tank
- 4 Electrical installation
- 5 Configuration
- 6 Operation and maintenance
- 7 Service and troubleshooting
- 7.1 Safety messages
- 7.2 Diagnostic messages
- 7.2.1 Device hardware fault – Device exchange
- 7.2.2 General power supply fault – Check availability
- 7.2.3 Device software fault – Check firmware revision
- 7.2.4 Parameter error – Check data sheet and values
- 7.2.5 Short circuit – Check installation
- 7.2.6 Device memory failure – Restore default settings
- 7.2.7 Level measurement lost – Check application
- 7.2.8 Simulation active – Check operational mode
- 7.2.9 Device temperature over-run – Clear source of heat
- 7.2.10 Device temperature under-run – Insulate device
- 7.2.11 Primary supply voltage over-run – Check tolerance
- 7.2.12 Primary supply voltage under-run – Check tolerance
- 7.2.13 Maintenance required - Cleaning
- 7.3 Troubleshooting incorrect level readings
- 7.3.1 Reported level is too high or low
- 7.3.2 Level is stuck in measuring range
- 7.3.3 Level is stuck in full tank
- 7.3.4 Level value drops when close to antenna
- 7.3.5 Measured level fluctuates
- 7.3.6 Measured level is occasionally unstable
- 7.3.7 Lagging of measured level
- 7.3.8 Incorrect level at 100% (20 mA)
- 7.3.9 Incorrect level when product surface is above 50%
- 7.3.10 Dropping of level close to tank bottom
- 7.3.11 Level measurement is lost in an empty tank
- 7.3.12 Alarm mode close to tank bottom
- 7.4 Managing disturbance echoes
- 7.5 Service and troubleshooting tools
- 7.6 Service support
- A Specifications and reference data
- A.1 Performance specifications
- A.2 Functional specifications
- A.3 Physical specifications
- A.4 Dimensional drawings
- B Product certifications
- C Configuration parameters
7.5.7 View holding registers
The holding registers store various transmitter parameters, such as configuration data,
used to control the measurement performance.
Procedure
1. Under
Menu, select Diagnosis → Read Holding Registers.
2. In the Holding Reg. Number box, enter the holding register to start reading from.
3. Select Write to device.
4. Select Read to device (not required in Rosemount IO-Link Assistant).
Five registers will be read, starting from the selected number.
7.5.8 Edit holding registers
The holding registers store various transmitter parameters, such as configuration data,
used to control the measurement performance.
Prerequisites
Note
Do not use holding registers to configure the transmitter unless you are qualified. This
dialog is mainly used for service purposes and for advanced configuration.
Procedure
1. Unlock the write protection of the holding registers.
a)
Under Menu, select Diagnosis → Write Holding Registers → Write Holding
Registers (Word).
b) In the Register Number box, enter 0.
c) In the Value (Word) box, enter 1234.
d) Select Write to device.
2. To edit a holding register value:
a) Under Write Holding Registers (Float) or Write Holding Registers (Word),
enter the register number and the corresponding value.
b) Select Write different values to device (Write to device in Rosemount IO-
Link Assistant).
3. Verify the written value by reading the holding register number.
4. Perform a device reset to write protect the holding registers.
Related information
Perform a device reset
Service and troubleshooting Reference Manual
September 2020 00809-0100-4480