Users Manual Part 1

Note
The surface echo is required to suppress the double bounce. If the surface echo enters the
Upper Null Zone, there is no product surface reference and the double bounce might be
interpreted as the surface echo.
The Double Bounce Handling function is only available in Rosemount Radar Master Plus.
Procedure
1.
Read the echo curve plot to determine if double bounce echoes are present.
2. Select Configure Level Setup Advanced.
3. Under More Advanced Options, select Echo Tracking.
4. In the Double Bounce Handling list, select Enabled or Disabled.
5. If you enabled Double Bounce Handling, then enter desired Double Bounce Offset.
6. Select Save.
Related information
Read the echo curve
Double bounce offset
The distance between each double bounce echo is constant. The Double Bounce Offset is
used to define the distance between detected double bounces, as given by the following
formula (see Figure 7-25):
Double Bounce Offset = B - 2A
The Double Bounce Offset is negative if the reflection point (normally the tank roof) is
below the Tank Reference Point.
7.6 Service support
To expedite the return process, refer to Emerson.com and contact the nearest Emerson
representative.
CAUTION
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of and understand the hazard. Returned products must include a copy of the
required Safety Data Sheet (SDS) for each substance.
Emerson representatives will explain the additional information and procedures necessary
to return goods exposed to hazardous substances.
Reference Manual Service and troubleshooting
00809-0100-4418