2. Select Configure Smart Echo.
3.
In the Smart Echo Level box, enter the desired value.
4. Select Save.
6.5.2 Perform a smart echo level test
During the test, a virtual surface echo is superimposed onto the radar signal, and the
transmitter will output a level corresponding to the echo position.
Prerequisites
This test is available for transmitters with:
Option code ET
Rosemount Radar Master Plus
Prior to and during the test, ensure that:
The product surface is calm.
The smart echo level is not closer than 1 ft. (0.3 m) to the liquid surface.
The tank is not being filled or emptied.
WARNING
During the test, the transmitter will not output measurement values corresponding to the
product surface level. Ensure systems and people relying on measurement values from the
transmitter are made aware of the changed conditions. Failure to do so could result in
death, serious injury and/or property damage.
Procedure
1.
Select Service Tools Proof Test.
2. Select Smart Echo Level Test.
3. Select Start and follow the on-screen instructions.
Postrequisites
When you have finished testing, select Stop to return to normal operation.
Related information
Simulation/test active
6.6 Smart meter verification
Smart Meter Verification is an automatic diagnostic tool that monitors the entire
transmitter’s performance and integrity without interrupting the process. The results of
this diagnostic provide a pass/fail summary report helping you to quickly identify and
resolve potential issues. Configuration changes since previous verification are tracked to
verify consistency of the device setup.