Users Manual Part 1

2. Check the number of table points to use is correct.
3.
If condition persists, restore default settings, and reconfigure the device.
Related information
Scaled variable
Restore to default settings
Configure transmitter using guided setup
Geometry configuration error
Cause
The configured tank geometry results in a too large level measuring range for this device.
Recommended actions
1. Check tank geometry configuration and reduce Reference Height.
2. If condition persists, restore default settings and reconfigure the device.
Related information
Reference height
Restore to default settings
Configure transmitter using guided setup
Primary variable configuration error
Cause
The Primary Variable selection is not supported.
Note
The IEC 61508 certified version only supports level or distance as Primary Variable.
Recommended actions
1.
Change Primary Variable to variable supported by device.
2. Consider purchasing an upgrade of the device to access additional variables.
Related information
Primary variable
Measurement correction configuration error
Cause
The factory measurement correction data is invalid.
Recommended actions
1. Restore default settings and reconfigure the device.
2. If the condition persists, replace the device.
Service and troubleshooting Reference Manual
September 2022
00809-0100-4418
60 Emerson.com/Rosemount