Users Manual Part 1

Related information
Calibrate analog out
SIS multidrop error
Cause
HART multidrop mode is not supported for safety (SIS) devices. Only 4-20 mA output is
supported for safety devices.
Recommended actions
1.
Disable multidrop mode.
2. Change Operational Mode to Control/Monitoring if device is not intended to be
used as safety device.
3. If the condition persists, restore default settings and reconfigure device.
Related information
Rosemount 3408 Safety Manual
Operational mode
Restore to default settings
Configure transmitter using guided setup
Engineering unit configuration error
Cause
One of the configured engineering units is not supported by the device.
Recommended actions
1. Check unit configuration.
2. If condition persists, restore default settings and reconfigure device.
Related information
Units
Restore to default settings
Configure transmitter using guided setup
Burst mode configuration error
Cause
The burst mode configuration is incorrect.
Recommended actions
1. Check configuration of burst mode.
2. If condition persists, restore default settings and reconfigure device.
Related information
Burst mode