7.3.1 Troubleshooting incorrect level readings
Reported level is too high or low
Figure 7-1: Symptom
A
B
C
D
A. Level
B.
Time
C. Actual level
D. Reported level
Possible cause
Incorrect tank geometry configuration.
Recommended actions
Verify the tank geometry parameters are configured correctly (especially the
Reference Height).
Run Verify Level to adjust level measurement.
Analyze the echo curve and check amplitude thresholds.
Restore default settings and reconfigure the device.
Related information
Reference height
Run verify level
Read the echo curve
Amplitude threshold
Restore to default settings
Service and troubleshooting Reference Manual