To set the resolution of the level trend timeline:
Procedure
1.
Select Service Tools Echo Curve.
2. Select Options.
3. In the Timeline Resolution list, select the desired length (in hours) of the timeline.
4.
Select Save.
5. Select Back.
7.4.2 Perform an analog loop test
During a loop test, the transmitter outputs a fixed value (4 mA, 20 mA, or user-selected
value).
The loop test command verifies the output of the transmitter, the integrity of the loop,
and the operations of any recorders or similar devices installed in the loop. A loop test can
also be used to determine the need for an analog output calibration.
Procedure
1.
Select Service Tools Simulate.
2. Under Analog Out, select Loop test, and then follow the on-screen instructions.
3. Measure the loop current.
Postrequisites
Select Stop or Cancel to exit loop test (Abort on handheld communicator).
Related information
Calibrate analog out
Simulation/test active
7.4.3 Calibrate analog out
Use this function to calibrate the analog output by comparing the actual output current
with the nominal 4 mA and 20 mA currents. Calibration is done at factory and the analog
output does not normally need to be recalibrated.
Procedure
1.
Select Service Tools Maintenance Routine Maintenance.
2. Select D/A trim (Calibrate Analog Out in Rosemount Radar Master Plus) and follow
the on-screen instructions.