Users Manual Part 1

6. Connect the cable wires.
0.3 in. (8 mm)
Note
When connecting a flexible (stranded) conductor, use a small screwdriver to press
down and hold the terminal connection open.
7. Ensure proper grounding.
8.
Tighten the cable gland.
Apply PTFE tape or other sealant to the threads.
Note
Make sure to arrange the wiring with a drip loop.
Electrical installation Reference Manual
September 2022
00809-0100-4418
34 Emerson.com/Rosemount