Transmitter Setup
4.1.3 Advanced Tank Geometry
Min. Level Offset C The C distance is used to extend the measurement
range beyond the Zero Level Reference Point down
to the tank bottom. C is defined as the distance
between the Zero Level and the tank bottom. Set
C=0 if you do not want to present negative levels
below the Zero Level reference point, or if you use
the tank bottom as zero level reference point.
Reference Distance G In most cases the LoopRadar Reference Point is
used as the upper reference point. However, the
LoopRadar gauge offers the option to use a nozzle
for hand dipping as the upper reference point.
G is the distance between the LoopRadar Refer-
ence Point and the Tank Ullage Reference Point.
The LoopRadar Reference Point is located at the
underside of the flange.
Tank height R The distance from the Tank Ullage Reference Point
to the Zero Level.
Level
LoopRadar Reference Point
H
Measuring Range
Product Surface
Ullage
C
R
Zero Level
Tank Ullage Reference Point
G