User's Guide
Table Of Contents
- Contents
- About this manual
- 1 Introduction
- The TankRadar Pro System
- Measurement Principle
- 2 Mechanical Installation
- Socket Requirements
- Free Space Requirements
- Dimensions
- Tools
- Mounting the Rod Antenna
- Mounting the Cone Antenna - PTFE sealing
- Mounting the Cone Antenna - Quartz Sealing
- Mounting the Cone Antenna - Process Seal
- Mounting the Parabolic Antenna
- 3 Electrical Installation
- Identication of Installed Options
- Junction Box
- External Connections
- Connecting to a TRL2 Bus Interface
- Connecting HART devices
- Connecting the Display Panel
- Cables
- Safety
- Power Supply
- Grounding
- System Overview
- Internal Connections
- 4 Pro Setup Software
- System Requirements
- Installing the Pro setup software
- Starting the Pro Setup Program
- Setting a Password
- Logging on to a password protected system.
- Setting measurement units
- Installing a Pro Transmitter
- Viewing Level Data
- Service
- 5 Using the Pro Display Panel
- Operation
- Viewing Level Data
- Installing a Pro Transmitter
- Service
- 6 Tank Distances
- Definitions
- Examples
- 7 Technical Information
- Technical Data
- Display Panel
- Analog Outputs
- 8 Troubleshooting
- Display Panel Error Messages
Saab TankRadar
®
Pro Troubleshooting
8-1
Edition 2. Ref. No: 306010E
8 Troubleshooting
SYMPTOM ACTION
No level reading Check the power supply.
Check the cables for serial data commu-
nication.
Incorrect level reading Check the transmitter calibration.
Check that the transmitter has not locked
on an interfering object.
Check that the mechanical installation is
correct.
Serial communication failure Check the COM port setting in the Pro
Setup program.
Check the serial communication address.
Check the cable connections and that the
correct cables are used.
Insufficient power supply to Field Bus
Modem.
Display Panel window is blank Check the power supply
Poor Display Panel contrast Press the two right-hand buttons to in-
crease the LCD contrast.