User's Guide
Table Of Contents
- Contents
- About this manual
- 1 Introduction
- The TankRadar Pro System
- Measurement Principle
- 2 Mechanical Installation
- Socket Requirements
- Free Space Requirements
- Dimensions
- Tools
- Mounting the Rod Antenna
- Mounting the Cone Antenna - PTFE sealing
- Mounting the Cone Antenna - Quartz Sealing
- Mounting the Cone Antenna - Process Seal
- Mounting the Parabolic Antenna
- 3 Electrical Installation
- Identication of Installed Options
- Junction Box
- External Connections
- Connecting to a TRL2 Bus Interface
- Connecting HART devices
- Connecting the Display Panel
- Cables
- Safety
- Power Supply
- Grounding
- System Overview
- Internal Connections
- 4 Pro Setup Software
- System Requirements
- Installing the Pro setup software
- Starting the Pro Setup Program
- Setting a Password
- Logging on to a password protected system.
- Setting measurement units
- Installing a Pro Transmitter
- Viewing Level Data
- Service
- 5 Using the Pro Display Panel
- Operation
- Viewing Level Data
- Installing a Pro Transmitter
- Service
- 6 Tank Distances
- Definitions
- Examples
- 7 Technical Information
- Technical Data
- Display Panel
- Analog Outputs
- 8 Troubleshooting
- Display Panel Error Messages
Saab TankRadar
®
ProPro Setup
4-20
Edition 2. Ref. No: 306010E
5 Select the Analog Outputs tab
1 Click the Read button.
Response: the current settings are displayed.
2 If your transmitter is equipped with a HART
®
modem select the
Analog Out1 tab. (Analog 1 is note available when using TRL2 Bus
communication).
3 Select the source to control the analog output.
4 Enter the range values that correspond to the analog output values
4 and 20 mA.
5 Enter the alarm mode, i.e the analog out state on measurement
error.
• High: the output current is set to 22 mA.
• Low: the output current is set to 3.8 mA.
• Hold Last Value: the output current is set to the present mea-
surement value at the time when the error occurred.
6 The analog output is calibrated at factory and does normally not
need to be recalibrated. However, if you still need to calibrate the
analog output current, click the Calibrate DAC button and follow
the instructions on the next page.
7 If your transmitter is equipped with an optional analog output select
the Analog Out2 tab and configure as described in steps 2 to 6.
8 Click the Store button to save the current settings.