User's Guide
Table Of Contents
- Contents
- About this manual
- 1 Introduction
- The TankRadar Pro System
- Measurement Principle
- 2 Mechanical Installation
- Socket Requirements
- Free Space Requirements
- Dimensions
- Tools
- Mounting the Rod Antenna
- Mounting the Cone Antenna - PTFE sealing
- Mounting the Cone Antenna - Quartz Sealing
- Mounting the Cone Antenna - Process Seal
- Mounting the Parabolic Antenna
- 3 Electrical Installation
- Identication of Installed Options
- Junction Box
- External Connections
- Connecting to a TRL2 Bus Interface
- Connecting HART devices
- Connecting the Display Panel
- Cables
- Safety
- Power Supply
- Grounding
- System Overview
- Internal Connections
- 4 Pro Setup Software
- System Requirements
- Installing the Pro setup software
- Starting the Pro Setup Program
- Setting a Password
- Logging on to a password protected system.
- Setting measurement units
- Installing a Pro Transmitter
- Viewing Level Data
- Service
- 5 Using the Pro Display Panel
- Operation
- Viewing Level Data
- Installing a Pro Transmitter
- Service
- 6 Tank Distances
- Definitions
- Examples
- 7 Technical Information
- Technical Data
- Display Panel
- Analog Outputs
- 8 Troubleshooting
- Display Panel Error Messages
Saab TankRadar
®
Pro Pro Setup
4-21
Edition 2. Ref. No: 306010E
Calibrating the Digital to Analog Converter (DAC)
The Digital to Analog Converter (DAC) is factory calibrated. How-
ever, if you want to check the calibration by measuring the output
current, do the following:
1 Click the Calibrate DAC... button.
2 Read the instruction and the warning.
Note! The analog output will be set to fixed current mode.
Make sure that control systems connected to the output are not
harmed.
3 Click the Set to 4 mA button.
4 Enter the measured output current and click the Store button.