00809-0300-4248, Rev AA
Appendix A: Specifications and Reference data
July 2014
Specifications and Reference Data
A.1.5 Ambient temperature effect
Table A-2. 248x Wireless Ambient temperature effects
Sensor
options
Sensor
reference
Input
range
Temperature effects per 1.0 °C (1.8 °F)
change in Ambient Temperature
Digital
accuracy
2-, 3-, 4-wire RTDs
°C °F
Pt 100
( = 0.00385)
IEC 751 –200 to 850 0.009 °C (0.0162 °F)
Entire Sensor Input
Range
Pt 200
( = 0.00385)
IEC 751 –200 to 850 0.012 °C (0.0216 °F)
Entire Sensor Input
Range
Pt 500
( = 0.00385)
IEC 751 –200 to 850 0.009 °C (0.0162 °F)
Entire Sensor Input
Range
Pt 1000
( = 0.00385)
IEC 751 –200 to 300 0.009 °C (0.0162 °F)
Entire Sensor Input
Range
Pt 100
( = 0.003916)
JIS 1604 –200 to 645 0.009 °C (0.0162 °F)
Entire Sensor Input
Range
Pt 200
( = 0.003916)
JIS 1604 –200 to 645 0.012 °C (0.0216 °F)
Entire Sensor Input
Range
Ni 120
Edison Curve
No. 7
–70 to 300 0.009 °C (0.0162 °F)
Entire Sensor Input
Range
Cu 10
Edison Copper
Winding No. 15
–50 to 250 0.06 °C (0.162 °F)
Entire Sensor Input
Range
Pt 50
( = 0.00391)
GOST 6651-94 –200 to 550 0.018 °C (0.0324 °F)
Entire Sensor Input
Range
Pt 100
( = 0.00391)
GOST 6651-94 –200 to 550 0.009 °C (0.0162 °F)
Entire Sensor Input
Range
Cu 50
( = 0.00426)
GOST 6651-94 –50 to 200 0.012 °C (0.0216 °F)
Entire Sensor Input
Range
Cu 50
( = 0.00428)
GOST 6651-94 –185 to 200 0.012 °C (0.0216 °F)
Entire Sensor Input
Range
Cu 100
( = 0.00426)
GOST 6651-94 –50 to 200 0.009 °C (0.0162 °F)
Entire Sensor Input
Range
Cu 100
( = 0.00428)
GOST 6651-94 –185 to 200 0.009 °C (0.0162 °F)
Entire Sensor Input
Range
Thermocouples
Type B
NIST Monograph
175, IEC 584
100 to 1820
0.0435 °C T 1000 °C
0.096 °C - (0.0075% of (T - 300)) 300 °C T < 1000 °C
0.162 °C - (0.033% of (T - 100)) 100 °C T < 300 °C
Type E
NIST Monograph
175, IEC 584
–50 to 1000 0.015 °C + (0.00129% of absolute value T) All
Type J
NIST Monograph
175, IEC 584
–180 to 760
0.0162 °C + (0.00087% of T) T 0 °C
0.0162 °C + (0.0075% of absolute value T) T < 0 °C
Type K
NIST Monograph
175, IEC 584
–180 to 1372
0.0183 °C + (0.0027% of T) T 0 °C
0.0183 °C + (0.0075% of absolute value T) T < 0 °C