Rosemount 708
2-2
DEVICE NETWORK
CONFIGURATION
To communicate with the Gateway, and ultimately the Information System, the
transmitter must be configured to communicate with the wireless network.
Using a Field Communicator or AMS, enter the Network ID and Join Key so
they match the Network ID and Join Key of the Gateway and the other
devices in the network. If the Network ID and Join Key are not identical, the
transmitter will not communicate with the network. The Network ID and Join
Key may be obtained from the Gateway on the Setup>Network>Settings
page on the web server. Using a 475 Field Communicator, the Network ID can
be configured by entering the Fast Key Sequence: X, X, X, X. The Join Key
can also be configured using a 475 Field Communicator with the Fast Key
Sequence: X, X, X, X.
The final device network configuration piece is the Update Rate which, by
default, is 1 minute. It can be changed at commissioning, or at any time, by
using AMS or the Gateway’s web server. The Update Rate should be
between 4 seconds and 60 minutes. To change the Update Rate with a Field
Communicator, use the Fast Key Sequence: X, X, X.
If doing a bench top initial configuration, after completion remove the power
module until installation. When the device is installed, insert he power module
and close the housing cover securely. Always ensure a proper seal so that
polymer touches polymer, but do not over tighten.
Figure 2-1. 708 Power Module
Connect the HART communication leads to the COMM terminals on the
power module.