Reference Manual
00809-0100-4102, Rev AA
Appendix A: Reference Data
June 2012
Specifications and Reference Data
A.3 Functional Specifications
A.3.1 Range and Sensor Limits
Zero and Span Adjustment Requirements
(HART and Low Power)
Zero and span values can be set anywhere within the range limits stated in Tab le A -1 .
Span must be greater than or equal to the minimum span stated in Ta ble A -1 .
Service
Liquid, gas, and vapor applications
4–20 mA (Output Code A)
Output
Two-wire 4–20 mA, user-selectable for linear or square root output. Digital process variable
superimposed on 4–20 mA signal, available to any host that conforms to the HART protocol.
Power Supply
External power supply required. Standard transmitter (4–20 mA) operates on 10.5 to 55 V dc with
no load.
Table A-1. 2051CD, 2051CG, 2051L, and 2051H Range and Sensor Limits
Range
Minimum Span Range and Sensor Limits
2051CD
(1)
,
CG, L, H
(1) Range 0 only available with 2051CD. Range 1 only available with 2051CD or 2051CG.
Upper
(URL)
Lower (LRL)
2051C
Differential
2051C/
Gage
2051L
Differential
2051L
Gage
2051H
Differential
0
0.1 inH
2
O
(0,25 mbar)
3.0 inH
2
O
(7,47 mbar)
–3.0 inH
2
O
(-7,47 mbar)
NA NA NA NA
1
0.5 inH
2
O
(1,2 mbar)
25 inH
2
O
(62,3 mbar)
–25 inH
2
O
(–62,1 mbar)
–25 inH
2
O
(–62,1 mbar)
NA NA NA
2
2.5 inH
2
O
(6,2 mbar)
250 inH
2
O
(0,62 bar)
–250 inH
2
O
(–0,62 bar)
–250 inH
2
O
(–0,62 bar)
–250 inH
2
O
(–0,62 bar)
–250 inH
2
O
(–0,62 bar)
–250 inH
2
O
(–0,62 bar)
3
10 inH
2
O
(24,9 mbar)
1000 inH
2
O
(2,49 bar)
–1000 inH
2
O
(–2,49 bar)
0.5 psia
(34,5 mbar abs)
–1000 inH
2
O
(–2,49 bar)
0.5 psia
(34,5 mbar abs)
–1000 inH
2
O
(–2,49 bar)
4
3 psi
(0,20 bar)
300 psi
(20,6 bar)
–300 psi
(–20,6 bar)
0.5 psia
(34,5 mbar abs)
–300 psi
(–20,6 bar)
0.5 psia
(34,5 mbar abs)
–300 psi
(–20,6 bar)
5
20 psi
(1,38 bar)
2000 psi
(137,9 bar)
– 2000 psi
(–137,9 bar)
0.5 psia
(34,5 mbar abs)
NA NA – 2000 psi
(–137,9 bar)