User's Manual
Table Of Contents
- 1. Introduction
- 2. Technical Specifications
- 3. Installation
- 4. Wiring Instructions
- 5. Reader Functionality
- 5.1 Transmit Mode
- 5.2 Programming the AYC-E/Q/T60 Series
- 5.2.1 Entering Programming Mode
- 5.2.2 Exiting Programming Mode
- 5.2.3 Selecting Keypad Transmission Format
- 5.2.4 Keypad Transmission Format Option Number
- 5.2.4.1 Option 1: Single Key, Wiegand 6-Bit (Rosslare Format)
- 5.2.4.2 Option 2: Single Key, Wiegand 6-Bit Nibble and Parities
- 5.2.4.3 Option 3: Single Key, Wiegand 8-Bit Nibbles Complemented
- 5.2.4.4 Option 4: 4 Keys Binary + Facility Code, Wiegand 26-Bit
- 5.2.4.5 Option 5: 1 to 5 Keys + Facility Code, Wiegand 26-Bit
- 5.2.4.6 Option 6: 6 Keys BCD and Parity Bits, Wiegand 26-Bit
- 5.2.4.7 Option 7: Single Key, 3x4 Matrix Keypad (MD-P64)
- 5.2.4.8 Option 8: 1 to 8 Keys BCD, Clock & Data
- 5.2.4.9 Option 9: Single Key, Wiegand 4-Bit
- 5.2.5 Selecting HID Prox Card Transmission Format
- 5.2.6 Selecting Rosslare PROX Card Transmission Format
- 5.2.7 Changing the Programming Code
- 5.2.8 Changing the Facility Code
- 5.2.9 Setting the Backlight Behavior
- 5.2.10 Setting the Reader Format
- 5.2.11 Return to Factory Default Settings
- 5.2.12 Replacing a Lost Programming Code
- 6. Controller Functionality
- 6.1 Normal, Secure, and Master Users
- 6.2 Modes of Operation
- 6.3 Changing the Modes of Operation
- 6.4 Auxiliary Input & Output
- 6.5 Door Alarms
- 6.6 Internal Case and Back Tamper
- 6.7 Lockout Feature (Keypad/Card Tamper)
- 6.8 REX Function
- 6.9 Secured Series Intelligent Power Supply
- 6.10 Programming the AYC-E/Q/T60
- 6.10.1 Entering Programming Mode
- 6.10.2 Exiting Programming Mode
- 6.10.3 Changing Lock Strike Code
- 6.10.4 Changing Auxiliary Code
- 6.10.5 Changing the Programming Code
- 6.10.6 Changing the Normal/Secure Code
- 6.10.7 Changing the Normal/Bypass Code and Door Chime Settings
- 6.10.8 Setting Fail Safe/Secure Operation, Tamper Siren and Lock Strike Release Time
- 6.10.9 Defining the Auxiliary Input and Output
- 6.10.10 Detailed Reference Guide
- 6.10.11 Setting the Lockout Feature
- 6.10.12 Setting the Backlight Behavior
- 6.10.13 Selecting the Rosslare PROX and HID Prox Format
- 6.10.14 Enrolling Primary and Secondary Codes
- 6.10.15 Deleting Primary and Secondary Codes
- 6.10.16 Relay Codes Assignment
- 6.10.17 PIN Code Length/Factory Default Settings
- 6.10.18 Replacing a Lost Programming Code
- 6.10.19 Replacing a Lost Normal/Secure Code
Controller Functionality
AYC-E/Q/T60 Family Installation and Programming Manual 53
6.10.10.6 Auxiliary Mode 5
Auxiliary input function: Door Monitor
Auxiliary output activated by: Shunt (explanation below)
For example, in Auxiliary Mode 5, the controller is capable of shunting
an alarm system. In this mode, the auxiliary input is to be wired to the
magnetic contact switch on the door. The auxiliary relay is wired to
the alarm system. Without a valid code entered, the auxiliary relay
matches the condition of the magnetic contact switch; if the door
opens, the auxiliary relay opens; if the door closes, the auxiliary relay
closes. When a valid code is entered, a countdown for maximum
shunt time, as defined by the auxiliary setting, begins; if the door is
not closed before the maximum shunt time, the alarm is triggered.
6.10.10.7 Auxiliary Mode 6
Auxiliary input function: Door Monitor
Auxiliary output activated by: Forced entry
For example, in Auxiliary Mode 6, the controller can trigger the
auxiliary relay if the door has been forced. If the siren settings are
enabled, the siren is activated.
In this mode, the auxiliary input functions as a door monitor switch
and is wired to the magnetic contact switch on the door. The auxiliary
relay is to be wired to the alarm system. If the door is forced open,
the controller waits for the period of the forced door delay time to
elapse and then it activates the auxiliary relay. The auxiliary setting
sets the forced door delay period.
6.10.10.8 Auxiliary Mode 7
Auxiliary input function: Door Monitor
Auxiliary output activated by: Door Ajar (door held open)
For example, in Auxiliary Mode 7, the controller can trigger the
auxiliary relay, if it detects that the door has been held open (ajar) too
long. In this mode, the auxiliary input functions as a door monitor
switch and is wired to the magnetic contact switch on the door. The
auxiliary relay is to be wired to the alarm system. If the door is
opened, the controller waits for the Door Ajar Delay time to elapse