Installation manual

17
RCT Models, 16 Feb 2012D Roth
Heating data based on 70F EAT; Cooling data based on 80/67F EAT. See Correction Factors on page 23 for different conditions.
EWT Flow
Aiflow HC HE LAT COP DH Aiflow TC SC HR EER DH
°F GPM PSI FT CFM MBtuh MBtuh °F W/W MBtuh CFM MBtuh MBtuh MBtuh
Btuh/W
MBtuh
1350 31.1 21.1 91.3 2.94 3.10 4.2
1500 31.4 21.3 89.4 2.95 3.12 4.2
1350 31.8 21.7 91.8 2.95 3.16 4.3
1500 32.1 22.0 89.8 2.98 3.16 4.3
1350 33.1 23.0 92.7 2.96 3.28 4.4
1500 33.6 23.4 90.7 2.99 3.29 4.5
1350 33.5 23.3 92.9 2.96 3.31 4.4
1500 33.9 23.7 90.9 2.98 3.33 4.5
1350 36.4 26.2 95.0 3.00 3.56 4.9
1500 36.9 26.6 92.8 3.01 3.60 5.0
1350 38.0 27.8 96.1 3.01 3.70 5.1
1500 38.4 28.1 93.7 3.02 3.73 5.1
1350 38.4 28.2 96.4 3.01 3.74 5.1
1500 38.8 28.5 94.0 3.02 3.77 5.4
1350 41.2 30.9 98.2 3.02 4.00 5.4 1400 50.3 34.3 0.68 57.4 2.08 24.1 4.0
1500 41.7 31.3 95.7 3.04 4.02 5.5 1550 51.1 36.1 0.71 58.5 2.16 23.7 4.2
1350 43.0 32.6 99.5 3.05 4.13 5.7 1400 51.5 34.7 0.67 58.1 1.93 26.6 3.8
1500 43.5 33.0 96.8 3.06 4.16 5.8 1550 52.4 36.6 0.70 59.3 2.01 26.1 4.0
1350 43.4 33.0 99.8 3.04 4.18 5.7 1400 51.9 34.8 0.67 58.4 1.91 27.1 3.6
1500 43.9 33.5 97.1 3.05 4.22 5.8 1550 52.8 36.7 0.69 59.5 1.98 26.7 3.8
1350 45.8 35.4 101.4 3.06 4.39 6.1 1400 49.0 33.8 0.69 57.0 2.35 20.8 4.9
1500 46.4 35.9 98.7 3.07 4.43 6.2 1550 49.8 35.6 0.71 58.1 2.44 20.4 5.2
1350 47.8 37.4 102.8 3.07 4.57 6.4 1400 50.2 34.3 0.68 57.6 2.18 23.0 4.7
1500 48.4 37.8 99.8 3.08 4.60 6.4 1550 51.1 36.1 0.71 58.8 2.27 22.5 5.0
1350 48.3 37.8 103.1 3.06 4.62 6.5 1400 50.6 34.4 0.68 57.9 2.15 23.5 4.5
1500 48.9 38.4 100.2 3.07 4.66 6.7 1550 51.5 36.2 0.70 59.1 2.24 23.0 4.7
1350 50.4 39.9 104.6 3.08 4.79 6.6 1400 47.0 33.0 0.70 56.0 2.65 17.7 5.8
1500 51.0 40.4 101.5 3.09 4.83 6.7 1550 47.8 34.9 0.73 57.1 2.75 17.4 6.1
1350 52.6 42.1 106.1 3.09 4.99 7.0 1400 48.2 33.6 0.70 56.6 2.47 19.5 5.6
1500 53.2 42.6 102.9 3.10 5.03 7.1 1550 49.0 35.4 0.72 57.7 2.56 19.1 5.9
1350 53.1 42.6 106.4 3.08 5.05 7.1 1400 48.5 33.7 0.69 56.8 2.44 19.9 5.3
1500 53.7 43.2 103.2 3.09 5.09 7.2 1550 49.4 35.5 0.72 58.0 2.53 19.6 5.6
1350 54.7 44.2 107.5 3.09 5.19 7.3 1400 44.4 32.1 0.72 54.7 3.02 14.7 6.7
1500 55.4 44.8 104.2 3.11 5.22 7.5 1550 45.1 33.9 0.75 55.8 3.13 14.4 7.1
1350 57.1 46.5 109.1 3.10 5.39 7.6 1400 45.5 32.5 0.71 55.1 2.80 16.2 6.3
1500 57.8 47.1 105.7 3.12 5.42 7.7 1550 46.3 34.4 0.74 56.3 2.90 16.0 6.8
1350 57.7 47.1 109.6 3.10 5.45 7.7 1400 45.8 32.6 0.71 55.3 2.76 16.6 6.2
1500 58.4 47.8 106.0 3.11 5.50 7.8 1550 46.7 34.5 0.74 56.4 2.86 16.3 6.5
1350 58.8 48.2 110.3 3.11 5.54 7.8 1400 41.5 30.9 0.75 53.2 3.42 12.1 7.5
1500 59.5 48.8 106.7 3.13 5.56 7.9 1550 42.2 32.6 0.77 54.3 3.55 11.9 7.9
1350 61.3 50.7 112.1 3.12 5.75 8.1 1400 42.6 31.4 0.74 53.5 3.18 13.4 7.1
1500 62.0 51.3 108.3 3.14 5.78 8.2 1550 43.3 33.0 0.76 54.6 3.30 13.1 7.5
1350 61.9 51.3 112.5 3.12 5.81 8.2 1400 42.9 31.5 0.73 53.6 3.14 13.7 7.0
1500 62.6 52.0 108.7 3.13 5.86 8.3 1550 43.6 33.2 0.76 54.7 3.25 13.4 7.4
1400 38.5 29.7 0.77 51.7 3.88 9.9 8.3
1550 39.2 31.2 0.80 52.9 4.02 9.8 8.7
1400 39.5 30.1 0.76 51.8 3.60 11.0 8.0
1550 40.1 31.7 0.79 52.8 3.73 10.8 8.4
1400 39.8 30.2 0.76 51.9 3.55 11.2 7.8
1550 40.4 31.8 0.79 52.9 3.68 11.0 8.2
1400 35.5 28.3 0.80 50.4 4.38 8.1 9.0
1550 36.1 29.8 0.83 51.6 4.55 7.9 9.5
1400 36.4 28.7 0.79 50.3 4.07 8.9 8.7
1550 37.1 30.2 0.82 51.5 4.22 8.8 9.2
1400 36.7 28.8 0.79 50.4 4.01 9.2 8.5
1550 37.3 30.3 0.81 51.5 4.16 9.0 8.9
WPD
Operation Not Recommended
Operation Not Recommended
Heatin
g
Coolin
g
kW S/T kW
12.9
3.0
8.5
12.5
2.8
7.9
11.3
2.5
5.6
1.3
3.7
5.4
1.2
3.4
4.9
1.1
6.0
10.0
12.0
70
80
90
100
110
25
30
40
50
60
12.0
6.0
10.0
12.0
6.0
6.0
10.0
12.0
10.0
12.0
3.2 7.4
4.6 10.6
1.1 2.5
12.0
6.0
10.0
3.0
2.8
2.7
6.0
10.0
12.0
6.0
10.0
12.0
6.0
10.0
12.0
6.0
10.0
12.0
0.9 2.1
6.5
4.1 9.5
1.0 2.3
6.9
4.3 9.9
1.0 2.3
2.5 5.8
3.6 8.3
2.5 5.8
3.7 8.5
0.9 2.1
2.6 6.0
3.8 8.8
0.9 2.1
6.2
3.9 9.0
Section 6j: Model 060 Performance Data: 5.0 Ton,
Part Load, 1550 CFM Cooling / 1500 CFM Heating