User's Manual

1669-R RFD OPERATOR MANUAL REV. PP1
35
5.3.6. To fire the Remote Units, press the “FIRE” switch. The operator should get
an indication of shot initiation. The ARMED light will go out and the green DISARMED
light for each selected Remote Unit will come on solid on the Controller Unit display
panel.
5.3.7. If not all the Remote Units were selected for the shot, repeat above steps to
initiate the remaining shots.
5.3.8. To disarm any Remote Units that have been armed, select the Remote Units
and press the “DISARM” switch. All selected Remote Units will return to the
DISARMED mode in approximately 3 seconds.
CAUTION Do not assume the Disarm command has been received by the Remote
Unit unless DISARMED status is confirmed with a steady DISARMED light for that
Remote Unit on the Controller Unit display panel. If distance appears to be the
problem, move closer to the Remote Unit following standard procedures for this type of
situation. The “STATUS” and/or “DISARM” switches may be pressed repeatedly as the
Remote Unit is approached. Maintain a safe distance from the Remote Unit. Do not
approach the Remote Unit until DISARMED status is confirmed with a steady
DISARMED light for that Remote Unit on the Controller Unit display panel. Under no
conditions should the “FIRE” switch be pressed as the Remote Unit is approached. DO
NOT bring the Controller Unit closer than 100 feet to blasting caps, wires connected to
blasting caps, or other explosives.
5.3.9. Turn off the Controller Unit.
5.3.10. Recover the fielded Remote Units.
5.3.11. Refer to Post Operational Procedures in chapter 5.5.14.
5.4. SYSTEM OPERATION – REMOTE UNITS MORE THAN 1 MILE FROM
CONTROLLER UNIT.
Note: If the distance between the Controller Unit and the Remote Units is in excess of
5 miles, the Remote Units status transmissions may not be received by the Controller
Unit. The Controller Unit will command the Remotes from a distance greater than 5
miles, but the Remote status may not be confirmed. The Controller Unit performs just
as it would when it is within 1 mile of the Remote Units. The only difference is the
method the status indications are displayed on the Controller Unit display panel. The
ARMED and DISARMED status lights for out of range Remote Units will flash on the
Controller Unit display panel to indicate the Controller Unit did not receive a status
message from the Remote Unit. Once the Remote Units are set up for the shot, the
operator must assume the Remote Units have received the command.
5.4.1. Ensure the area is clear.
5.4.2. Turn the Controller Unit on.