Instruction Manual

HC2-S3C0X Meteorological Probe
HC2-S3C0X-PTxx Meteorological Probe with passive Pt100
General description
Your ROTRONIC probe is designed according to ISO 9001 and meeting EN61000-6-4 and
EN61000-6-2 EMC requirements. The probe works perfectly for many years when you follow
the operating guidelines.
These short instructions are limited to a description of the main functions and installation of
the device. The detailed instruction manual can be found on the internet at:
www.rotronic-humidity.com
HC2-S3C0X HC2-S3C0X-PTxx
Cable length in meter Pt type
Technical Data
Operating & measuring range: 0...100 %rh / -50…100 °C
Outputs (factory default): 0… 1 V = -40...60 °C / 0…100 %rh
Digital output: UART
Start-up time / Measurement interval: 1.5 s / 1 s
Supply voltage / Load: 5…24 VDC / 5…16 VAC / > 1 kOhm
Accuracy at 23 °C: HC2-S3C0X: ±1 %rh / ±0.2 K
HC2-S3C0X-PTxx: ±1 %rh / ±0.1 K (passive)
Protection rating: IP65 (except sensor / fi lter area)
HC2-S3C0X-
SERIES
SHORT INSTRUCTION MANUAL
Wire colours
HC2-S3C0X HC2-S3C0X-PTxx HC2-S3C0X-PTxx
Green Power +, max 24 VDC Power +, max 24 VDC Pt100 wiring
Gray GND (digital and power) GND (digital and power)
Red RxD (UART) RxD (UART)
Blue TxD (UART) TxD (UART)
White Analogue signal %rh Analogue signal %rh
Brown Analogue signal °C Analogue signal °C
Shield Not connected on probe side AGND (analogue ground)
Black Ptxx
Purple Ptxx
Yellow AGND (analogue ground) Ptxx
Orange Ptxx
Calibration and Adjustment
The probe has been factory-adjusted and comes with a calibration certifi cate. We recommend
calibration after about 1 year, depending on use. For probe adjustment instructions, contact
ROTRONIC or the ROTRONIC representative in your country.
Dimensional Diagram
The electronics of the probe is sensitive to electrostatic discharge (ESD) and wrong supply
polarity. Make sure to be properly earthed when handling the probe. Improper handling and
too high supply voltage as well as wrong connections (supply voltage on signal wires) may
destroy the probe. This can be traced and will void warranty!
Accessories for programming and calibration the device
AC3001-XX USB cable with open end to connect the probe to a PC
AC3002-XX RS-232 cable with open end to connect the probe to a PC
ROTRONIC AG, CH-8303 Bassersdorf, Tel. +41 44 838 11 44, www.rotronic-humidity.com
ROTRONIC Messgeräte GmbH, D-76275 Ettlingen, Tel. +49 7243 383 250, www.rotronic.de
ROTRONIC SARL, 56, F - 77183 Croissy Beaubourg, Tél. +33 1 60 95 07 10, www.rotronic.fr
ROTRONIC Instruments (UK) Ltd, Crompton Fields, Phone +44 1293 571000, www.rotronic.co.uk
12.0 816 .06 00
black
purple
yellow
orange