In general, signal cables should be installed in bundles or channels / conduits, separate from other cables as
indicated in the table below:
Bus signals such as RS-485
Data signals for PCs, printers, etc.
Shielded analog inputs
Unshielded DC voltage ( 60 V)
Shielded process signals ( 25 V)
Unshielded AC voltage ( 25 V)
Coaxial cables for CRT monitors
in common bundles or channels / conduits
DC voltage from 60 V to 400 V (unshielded)
AC voltage from 25 V to 400 V (unshielded)
in separated bundles or channels / conduits,
without minimum distance
DC and AC voltage > 400 V (unshielded)
Telephone lines
Lines leading into EX-rated areas
in separated bundles or channels / conduits