Installation Guide

507052-04Page 18 of 53 Issue 1727
A95DF2V & 95G2DFV Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4,500 ft
Number of
90° Elbows
Used
2nd Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity
045 070 090 110 045 070 090 110 045 070 090 110
1 66 51 29 9 100 100 78 43 123 122 103 103
2 61 46 24
n/a
95 95 73 38 118 117 98 98
3 56 41 19 90 90 68 33 113 112 93 93
4 51 36 14 85 85 63 28 108 107 88 88
5 46 31 9 80 80 58 23 103 102 83 83
6 41 26
n/a
75 75 53 18 98 97 78 78
7 36 21 70 70 48 13 93 92 73 73
8 31 16 65 65 43 8 88 87 68 68
9 26 11 60 60 38
n/a
83 82 63 63
10 21 6 55 55 33 78 77 58 58
Standard Termination at Elevation 4,501 - 10,000 ft
Number of
90° Elbows
Used
2nd Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity
045 070 090 110 045 070 090 110 045 070 090 110
1 66 51 29
n/a
100 100 78 43 123 122 103 103
2 61 46 24 95 95 73 38 118 117 98 98
3 56 41 19 90 90 68 33 113 112 93 93
4 51 36 14 85 85 63 28 108 107 88 88
5 46 31 9 80 80 58 23 103 102 83 83
6 41 26
n/a
75 75 53 18 98 97 78 78
7 36 21 70 70 48 13 93 92 73 73
8 31 16 65 65 43 8 88 87 68 68
9 26 11 60 60 38
n/a
83 82 63 63
10 21 n/a 55 55 33 78 77 58 58
*Size intake and exhaust pipe length separately. Values in table are for intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
Table 7A.