INSTALL SHEET
OUV OUTDOOR UNIVERSAL VIEWER
Programming/RF Testing/Mounting
The following provides summarized steps for device
programming, testing, and mounting. For complete details,
refer to the control panel installation manual.
1 Put control panel into Programming/Configuration mode.
2 Using a programmed alphanumeric keypad, proceed
through menus until the display shows ADD A NEW DEVICE.
3 Press OK/YES. the display shows PRESS PROGRAM
BUTTON OF DEVICE.
4 Apply a voltage on the OUV programming pin (6) through
the connected detection device par l’intermédiaire de
l’équipment connecté.
The OUV blinks.
5 Wait for keypad display to show CAMERA(1 - 25)
PROGRAMMED. Press OK/YES, the display shows RADIO
RANGE TEST? Press OK/YES again. The camera LED starts
flashing and keypad display shows RF TEST.
6 Take the OUV module to its intended mounting location
and make sure LED flashes continuously or you receive a 9/9
indicating good communication with the control panel.
7 Press OK/YES to end radio range test then press ESC/NO.
8 The keypad displays :
AREA ALLOCATION :
AREA : 1
Press either arrow button repeatedly until desired area number
appears then press OK/YES. By default all devices in Area 1 are
automatically delayed.
9 The display shows NAME + LOCATION:
Enter appropriate device name/location (up to 16 characters),
then press OK/YES. The display shows the device number and
name for your verification.
10 Install the OUV and its detector. Follow the detector
manufacturer mounting instructions.
11 Press OK/YES. The display shows FUNCTIONAL DEVICE
TEST? Press OK/YES and verify camera operation. The
activation of the LED will determine the detection field.
12 Press OK/YES to end detection verification.
13 The display shows OPERATION COMPLETED or ADD A
NEW DEVICE? Press YES/OK. Repeat steps 1 – 12 for remaining
cameras.
14 When finished, exit from configuration mode.
Pin Name Function Notes and setting
1 Vcc Input voltage 2.8 to 5 V
DC
2 GND Ground 0 V
3 Detect Intrusion detection State 1 (>2V
DC
) during 100 ms while powering the OUV
4 Trouble Communication lost
5 Armed System armed The connected detector must ignore that pin at startup
6 Config Programming button
7 Ext-trouble Problem on the connected detector State 0 (<0.5V
DC
) during 100 ms while powering the OUV
8 IR-ON Infrared illumination activation