Specifications
RTS 2nd Generation SERVO AMPLIFIER
38
PVD 3487 GB 03/2004
4.5 Terminal block X2 connection
Recommended cable cross-section : 0.5 - 1.5 mm²
DESCRIPTION
N° NAME
TERMINAL BLOCK X2
1
2
3
4
5
+15 V
0V
-15V
READY
READY
O
-
O
O
± 15 V (25 mA) available for external
applications.
Output via contact of sum of faults.
Contact opens if fault or mains failure
occurs.
Permissible current : 0.5 A
Permissible voltage : 220 V ac
4.6 Terminal block X3 connection
Recommended cable cross-section :
RTS 3/10 : 1.5 mm²; RTS 10/20, 12/24, 16/32, 20/40 : 2.5 mm²
DESCRIPTION
N° NAME
TERMINAL BLOCK X3
1
2
3
4
5
6
M-
M+
U ≈
V≈
W≈
O
I
I
I
-
Motor connection, cable cross-
section to be used (see motor
dimensions section). Minimum motor
inductance must be 0.4 to 1 mH
depending on RTS rating.
Phase U of three-phase supply. For
single-phase supply, this input is not
connected.
Phase V.
Phase W
Ground to be wired to cabinet ground
rod by minimum 2.5 mm² lead.
TERMINAL
TERMINAL