User Manual

13
General Specications
H. GENERAL SPECIFICATIONS
Table6 – General Specications
Nominal kW
2 3 4 5 7. 5 10 15 20 25 30
Fan Diameter
in. 10 14
mm 254 356
Air Delivery
CFM 460 465 475 480 590 760 1040 1260 1500 1500
m³/min 13 13 14 14 17 17 29 37 43 43
Horizontal Throw
ft. 20 47
m 6 14.3
Normal Mounting Height*
(to underside)
ft. 6.0 to 8.0 8.0 to 12.0
m 1.8 to 2.4 2.4 to 3.6
Shipping Weight
lbs 59 104
kg 24 47
Note*: *Recommended mounting height to ensure warm air reaches the oor.