User Manual

4
Installation
FRONT VIEW
2¼"
B
A
HEATING ELEMENTS
REAR VIEW
MOTOR
1/2" x 3/4" MULTIPLE
CONDUIT ENTRY
1" x 1-1/4" MULTIPLE
CONDUIT ENTRY
'W' HOLE
Table1 – Heater & Bracket Dimensions
Dim.
2-10 kW 15 30 kW
in. mm in. mm
A 17 432 24 610
B 14 356 19 1/2 495
C (Depth) 15 1/2 394 22 559
R (Hole dia.) 1/2 13 5/8 16
S 12 1/2 318 17 1/2 445
T 4 1/2 114 6 152
U 4 1/2 114 6 152
W (Hole dia.) 3/4 19 3/4 19
Figure 1
Figure2 – Mounting Clearance
CEILING MOUNT
WITH CLEARANCES
6” (152mm) MIN.
CEILING
CLEARNACE
WALL MOUNT
BRACKET HOLE
PATTERN
T
U
'R' HOLE
FRONT VIEW
BRACKET HOLE
U
'D
WALL MOUNT
WITH CLEARANCES
3.5" (89 mm) for 2 to 10 kW
6.0” (152 mm) for 15 to 30 kW
MINIMUM WALL CLEARANCE
72”
(1830 mm)
DISCHARGE
DISTANCE
C
MOUNTING ARM
S
72”
(1830 mm)
MINIMUM
B
A
B.2  Mounting
1. The heater must be permanently mounted to a xed 
location onto a wall or ceiling.
2. The mounting surface must be strong enough to:
Support the heater’s weight.
Provide sufcient stiffness to prevent excessive 
vibration.
3. The single bolt mounting is not designed for high dynamic
loads that can occur during transportation. For heaters
that are to be installed prior to transportation, it is
recommended that temporary blocking or strapping be
used to limit movement of the heater with respect to the
mounting structure. Inspection of the mounting bolt for
correct tensioning is also recommended after arrival at site
to ensure no loosening has occurred in transportation. The
mounting bolt/nut should be torqued to 65 – 75ft‑lbs, refer 
to Table5, page11.
4. Install the bracket on the heater with hardware provided.
4.1 Orient the heater to its nal position before 
tightening all hardware.
4.2 In higher vibration installations use of a removable
thread locking compound such as Loctite® 243
Blue Threadlocker is recommended.
4.3 Correct tensioning of the mounting bolt will include
full compression of the split lock washer and
inspection for correct thread engagement. The
mounting bolt/nut should be torqued to 65 – 75ft‑lbs, 
refer to Table5, page11.
5. The discharge air louvers are individually adjustable.
(57 mm)
72”
(1830 mm)
MINIMUM
Table2 – Installation Height & Heater Weight
kW
Recommended Mounting
Height - ft (m)
Heater Weight
lbs (kg)
2 – 1 0 6 to 8 (1.8 to 2.4) 53 (24)
15 – 30 8 to 12 (2.4 to 3.6) 104 (47)
WARNING
WARNING. Install heater with suffcient clearance to walls
and ceiling as indicated in gure 2 on page 4. Mount with 
bottom of heater no less than 6 ft (1830 mm) above oor 
or grade.