User guide

Type Tests
42
RuggedCom
®
RuggedServer RS416 Family Installation Guide rev118
7.2 IEEE 1613 Type Tests
IEEE Test
IEEE
1613
Clause
Description Test Levels
C37.90.3 9 ESD
Enclosure Contact +/- 8kV
Enclosure Air +/- 15kV
C37.90.2 8 Radiated RFI Enclosure ports 35 V/m
C37.90.1 7 Fast Transient
Signal ports +/- 4kV @ 2.5kHz
D.C. Power ports +/- 4kV
A.C. Power ports +/- 4kV
Earth ground ports +/- 4kV
C37.90.1 7 Oscillatory
Signal ports 2.5kV common mode @ 1MHz
D.C. Power ports 2.5kV common & differential mode @ 1MHz
A.C. Power ports 2.5kV common & differential mode @ 1MHz
C37.90 6 H.V. Impulse
Signal ports 5 kV (Failsafe Relay)
D.C. Power ports 5 kV
A.C. Power ports 5 kV
C37.90 6
Dielectric
Strength
Signal ports 2kVAC
D.C. Power ports 1.5kVDC
A.C. Power ports 2kVAC
Table 25 - IEEE 1613 Type Tests
Notes:
If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (During
disturbance, errors may occur but recovery is automatic).
If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (During
disturbance, no errors will occur).
7.3 IEC Environmental Type Tests
Test Description Test Levels
Severity
Levels
IEC 60068-2-1
Cold
Temperature
Test Ad -40 deg. C, 16 Hours N/A
IEC 60068-2-2 Dry Heat Test Bd +85 deg. C, 16 Hours N/A
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing), 55°C, 6
cycles
N/A
IEC 60255-21-1 Vibration 2g @ (10-150) Hz Class 2
IEC 60255-21-2 Shock 30g @ 11 ms Class 2
Table 26 - Environmental Type Tests