Installation Guide

Table Of Contents
1. Apply AC power to the unit. The LED Indicator should turn RED.
2. After the battery has been left to charge for 24 hours, tesdt the unit by pushing the switch. The LED indicator
turns off and the LED board stays ON.
3. When the switch is released, the LEDs turn OFF and the LED indicator turns back to RED.
Caution: Always turn off Acpower to the equipment before servicing. Servicing should be performed only by a
qualied service technician. Use only MANUFACTURE supplied replace cerrent parts.
BATTERY: The battery supplied with the battery backup model requires no maintenance. However, it should be
tested periodically(see TESTING) and replaced when it no longer operates the connected fixtures for the duration
of a 30 second or 90 minutes test. The battery supplied in this equipment has a life expectancy of 5 years when
used in a normal ambient temperature of 72 F.
National Electric Code (NEC) and NFPA life safety code regulations require that routine tests need to be performed
as listed below:
Once every month, the unit needs to be tested for duration of 30 seconds. Push in and the test switch to perform
this test.
Once every 12 months, a full 90 minutes (per UL requirements)test needs to be performed on the unit. Disconnect
power to the unit and leave it in the emergency mode. The LEDS should stay ON for at least 90 minutes.
MAINTENANCE:
OPERATION (Batter y Backup):
TESTING:
Page 2 of 2