TABLE 6
L
IQUID LINE SIZE OUTDOOR UNIT ABOVE INDOOR COIL
Liquid Line Size
Outdoor Unit Above Indoor Coil
(Cooling Only - Does not apply to Heat Pumps)
S
ystem
Capacity
Line Size
C
onnection
Size
(Inch I.D.)
L
ine Size
(Inch O.D.)
Total
Minimum Vertical Separation - Feet
25 50 75 100 125 150
1/4 25 40 25 9 N/A N/A
1
1
2 Ton 3/8 5/16 25 50 62 58 53 49
3/8* 25 50 75 72 70 68
1/4 23 N/A N/A N/A N/A N/A
2 Ton 3/8 5/16 25 36 29 23 16 9
3/8* 25 50 72 70 68 65
1/4 25 N/A N/A N/A N/A N/A
2
1
2 Ton 3/8 5/16 25 49 38 27 17 6
3/8* 25 50 68 65 62 58
5/16 25 50 37 22 7 N/A
3 Ton 3/8
3/8* 25 50 68 63 58 53
5/16 25 23 4 N/A NA N/A
3
1
2 Ton 3/8
3/8* 25 50 43 36 30 24
3/8* 25 46 38 30 22 15
4 Ton 3/8
1/2 25 50 56 55 53 52
3/8* 25 50 56 44 32 20
5 Ton 3/8
1/2 25 50 75 81 79 76
*Standard Line Size
N/A - Application not recommended.
Liquid Line Size
Outdoor unit below Indoor Coil
System
Capacity
Line Size
Connection
Size
(Inch I.D.)
Line Size
(Inch O.D.)
Total
Maximum Vertical Separation - Feet
25 50 75 100 125 150