User`s manual
INSTALLERUSERTECHNICIAN
1010
Caution: if the exhaust terminal and/or extension
concentric pipe needs shortening, consider that the
internal duct must always protrude by 5 mm with
respect to the external duct.
Normally the horizontal intake/exhaust kit Ø 80/125
is used in the event of using particularly long
extensions; the kit Ø 80/125 can be installed with a
rear, right-hand, left-hand or front outlet.
• Extensions for horizontal kit. The horizontal intake/
exhaust kit Ø 80/125 can be extended up to a
maximum horizontal length of 7300 mm including
the terminal grille and excluding the concentric
bend on output of the boiler and the adapter Ø 60/
100 in Ø 80/125 (see figure). This configuration
corresponds to a resistance factor of 100. In this
case special extensions must be requested.
N.B.: when installing the ducts, a section clamp
with pin must be installed every 3 metres.
• External grille. The intake/exhaust terminal models
Ø 60/100 and Ø 80/125, if correctly installed, blend
with external building aesthetics. Ensure that the
silicon washer is fitted snugly against the external
wall.
N.B.: for safety purposes, do not totally or partially
obstruct the boiler intake/exhaust terminal even
temporarily.
Vertical kit with aluminium tile Ø 80/125. Kit
assembly: install the concentric flange (2) on the
innermost hole of the boiler taking care to insert the
seal (1) supplied with the kit and tighten by means of
the screws supplied with the boiler. Fit the male
section (smooth) of the adapter (3) coin the female
section of the concentric flange (2). Installing the
imitation aluminium tile. Replace the tile with the
aluminium sheet (5), shaping it to ensure off-flow of
rainwater. Position the fixed half-shell (7) on the
aluminium tile and insert the intake/exhaust pipe (6).
Fit the concentric terminal Ø 80/125 (6) with the male
section (smooth) in the female section of the adapter
(3) (with lip seals) to the end stop, ensuring that the
washer (4) is fitted to ensure sealing efficiency of all
couplings.
• Snap fit extension pipe fittings and concentric
elbows. To install snap-fit extensions with other
elements of the boiler assembly, proceed as
follows: fit the concentric pipe or elbow with the
male section (smooth) on the female section (with
lip seals) to the end stop on the previously installed
element to ensure sealing efficiency of the coupling.
Caution: if the exhaust terminal and/or extension
concentric pipe needs shortening, consider that the
internal duct must always protrude by 5 mm with
respect to the external duct.
This specific terminal enables flue exhaust and air
intake in a vertical direction.
N.B.: the vertical kit Ø 80/125 with aluminium tile
enables installation on terraces and roofs with
maximum gradient of 45% (24°) and the height
between the terminal cap and half-shell (374 mm)
must be strictly observed.
This vertical kit configuration can be extended to a
maximum length of 12200 mm in a vertical straight
route, including the terminal (see figure below). This
configuration corresponds to a resistance factor of
100. In this case specific extensions must be
requested.
Terminal Ø 60/100 can also be used for vertical
exhaust, in conjunction with concentric flange code
no. 3.011141 (sold separately). Height between the
terminal cap and half-shell (374 mm) must be strictly
observed (see drawing below).
This vertical kit configuration can be extended to a
maximum length of 4700 mm in a vertical straight
line, including the terminal (see figure below).
The kit comprises:
N
°
1 - Seal (1)
N
°
1 - Female concentric
flange (2)
N
°
1 - Adapter Ø 60/100 for Ø
80/125 (3)
N
°
1 - Washer(4)
N
°
1 - Aluminium tile (5)
N
°
1 - Int./Exh. concentric pipe
Ø 80/125 (6)
N
°
1 - Fixed half-shell (7)
N
°
1 - Mobile half-shell (8)