User`s manual
INSTALLERUSERTECHNICIAN
1212
36.0*
INSULATED DUCT
Maximum effective lengths
(including intake terminal with grille and two 90° bends)
Intake (metres)
NON-INSULATED DUCT
Exhaust (metres)
Intake (metres) Exhaust (metres)
29.5*
16
28.0*
2
34.5* 7
26.5*
3
33.0* 8
25.5*
4
32.0* 9
24.0*
5
30.5* 10
22.5*
11
21.5*
12
* The intake duct can be increased by 2.5 metres if
the bend on exhaust is eliminated, 2 metres if the
intake bend is eliminated or 4 metres of both bends
are removed.
N.B.: when installing the Ø 80 ducts, a section clamp
with pin must be installed every 3 metres.
Insulated separator kitØ 80/80. Kit assembly: install
flange (4) on the central hole of the boiler taking
care to insert the seal (1) supplied with the kit and
tighten by means of the screws on the boiler. Remove
the flat flange on the outermost hole and replace with
flange (3) inserting seal (2) already fitted on the boiler
and tighten with the screws supplied. Insert and slide
cap (6) onto bend (5) on the male section (smooth)
and join bends (5) with the male section (smooth in
the female section of flange (3). Fit bend (10) with
the male section (smooth) in the female section of
flange (4). Join the intake terminal (7) with the male
section (smooth) in the female section of bend (5) to
the end stop, ensuring that washers (8) are inserted
to achieve correct installation between the pipe and
wall and fit the end cap (6) on terminal (7). Join the
exhaust pipe (9) with the male section (smooth) in
the female section of the bend (10) to the end stop,
ensuring that the washer (8) is already inserted for
correct installation between the pipe and flue.
The kit comprises:
N
°
1 - Seal (1)
N
°
1 - Flange seal (2)
N
°
1 - Female intake flange (3)
N
°
1 - Female exhaust flange (4)
N
°
1 - 90
°
bend Ø 80 (5)
N
°
1 - Pipe end cap (6)
N
°
1 - Insulated intake terminal Ø 80 (7)
N
°
3 - Washers (8)
N
°
1 - Insulated exhaust pipe Ø 80 (9)
N
°
1 - Concentric 90
°
bend Ø 80/125 (10)
A=INTAKE
B=EXHAUST