ENERGY RECOVERY TOTAL RECOVERY VENTILATORS Balanced Ventilation for Residential and Commercial Buildings ERV-102819 October 2019 Advancing Ventilation™
INDOOR AIR QUALITY As buildings are being built with higher quality construction methods, balanced ventilation methods are more important than ever. An unbalanced home results in poor Indoor Air Quality (IAQ), causing poor conditions for your home and the inhabitants. Americans spend of their time INDOORS. As codes change, it is important for you to understand why Indoor Air Quality is so important and the options available to you from S&P USA.
HOW ERVs WORK With S&P’s TR, TRLPe & TRC (Total Recovery) ERV Series for all climates, stale room air is exhausted and fresh outdoor air is brought back into the building. These two air streams are directed through a highly developed enthalpic air-to-air energy exchange core. The air streams are physically separated by many layers of plates so there is no mixing or contamination of the fresh air.
THE S&P ADVANTAGE 5TH GENERATION CORE • Efficient transfer of heat and moisture • No liquid is accumulated; no drain pan or defrost mechanism is required! • Contaminated air is exhausted from the building, while the static plate core regulates extremes in humidity • Industry best 10-year warranty 10 YEAR CORE WARRANTY S&P TR, TRLPe and TRC are protected by a 10-year core warranty (2 years on balance of the unit).
MODEL TR, TRe, TRC, AND TRCe SIZING CHOOSING THE RIGHT SIZE TR Based on square footage Sq. Ft. Model TR90 and TR90G Models TR130, TR200 and TR300 <1500 Models TRLPe100 and TRLPe100C 1501-2700 2701-4000 4001-6000 Model TRC500 and TRCe500 CHOOSING THE RIGHT SIZE TR OR TRC Based on Air Handler Load Ton Model TRC800 and TRCe800 (Vertical Configuration Available) Model Needed TR90/TR90G/ TRLPe100/ TRLPe100C TR130 TR200 TR300 1.0 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.5 8.0 12.0 13.
TR+ TRe SERIES MODELS MODEL TR90/TR90G SPECIFICATIONS LISTED DUCTED HEAT RECOVERY VENTILATOR 89S5 Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 40-110 CFM TR90 - Painted Case, Low Voltage Controls, Line Cord TR90G - Galvanized Case, Line Voltage, No Line Cord; No Control Board Unit may be mounted in any orientation and in heated or unheated locations Number Motors: Two, 0.
MODEL TR130 SPECIFICATIONS Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 50-140 CFM Unit may be mounted in any orientation Number Motors: One, 0.1 hp V Hz Phase Input Watts 120 60 Single 102 @ 130 CFM FLA per motor 1.3 Control Voltage: 24 VAC transformer / relay package with switched dry contacts Filters: MERV 8, spun polyester media.
MODEL TR300 SPECIFICATIONS Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 150-300 CFM Unit may be mounted in any orientation Number Motors: One, 0.2 hp V 120 Hz 60 Phase Single Input Watts 315 @ 297 CFM FLA 3.3 Control Voltage: 24 VAC transformer Filters: MERV 8, spun polyester media.
Model TRCe500 SPECIFICATIONS Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 200-540 CFM AHRI 1060 Certified Core: One L85 Airflow Rating Points (for AHRI): 450 CFM and 338 CFM Motors: One, 0.5 hp (Single Phase) FLA Min. Cir. Max Overcurrent V Hz Phase per Protection Device Amps motor 120 60 Single 8.1 10.1 15 208-230 60 Single 4.8 6.
Model TRC800V SPECIFICATIONS Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 250-925 CFM AHRI 1060 Certified Core: One L125-G5 Airflow Rating Points (for AHRI): 750 CFM and 563 CFM Motors: Two, 0.75 HP, direct drive blower/motor packages V Hz Phase FLA per motor Min. Cir. Amps Max Overcurrent Protection Device 120 60 Single 9.0 20.3 25 208-230 60 Single 4.5 10.
Model TRCe800V SPECIFICATIONS Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 250-1,100 CFM AHRI 1060 Certified Core: One L125-00 Airflow Rating Points (for AHRI): 750 CFM and 563 CFM Motors: Two, 0.5 HP, direct drive blower/motor packages V Hz Phase FLA per motor Min. Cir. Amps Max Overcurrent Protection 115 60 Single 8.1 18.2 25 208-230 60 Single 4.8 10.
MODEL TRCe1200 SPECIFICATIONS Ventilation Type: Static Plate, Heat and Humidity Transfer Typical Airflow Range: 375-1,575 CFM AHRI 1060 Certified Cores: One L62-G5 and one L125-G5 Motors: Qty 2, 1.0 HP ea., Direct Drive EC blower/motor package Min. Cir. Amps Max. Overcurrent Protection Device V Hz Phase FLA per motor 120 60 Single 8.0 18.0 20 208-230 60 Single 6.2 Standard Features: Non-Fused Disconnect 14.0 15 Drive HP 1.
TR+ TRLPe SERIES ACCESSORIES SPTL - PERCENTAGE TIMER CONTROL-SPTL - • • • • Primary control for TR90, TRLPe100, TRLPe100C, TR130, TR200 and TR300 Runs unit an adjustable amount of time each hour Two wire, low voltage connection to TR Meets ASHRAE 62.
TRC SERIES ACCESSORIES DIGITAL TIME CLOCK - WALL MOUNT - STC7D-W • Up to 8 on/off cycles per day or 56 per week • 24 VAC power requirement • Battery back-up • Fits any 4” x 4” electrical box MOTION (OCCUPANCY) CONTROL - CEILING MOUNT- SMC-C • Passive infared sensor • Adjustable time-off delay to 30 minutes • 24 VAC power requirement • Covers up to 1500 sq. ft.
S&P USA Ventilation Systems, LLC 6393 Powers Avenue Jacksonville, Florida 32217 T. 904.731.4711 | F. 904.737.8322 www.solerpalau-usa.com S&P Canada Ventilation Products Inc 6710 Maritz Drive Unit #7 Mississauga, ON L5W T. 416.744.1217 | F. 416.744.0887 www.solerpalaucanada.