Datasheet
10
G
RHEASREG
®
KLSW ⁄ RHEASGARD
®
KLGF
Rev. 2017 - V13 GB
The electronic airflow monitor
RHEASGARD
®
KLGF
measures the flow velocity in m ⁄ s and converts the measurement signal into a standard signal
of 0 - 10 V (flow measuring transducer). This flow sensor is optionally available with or without display.
RHEASREG
®
KLSW
provided with a switching output (one-step or two-step) is designed as flow sensor ⁄ flow monitor. Fine adjustment of the upper
range limit by the user is possible at a potentiometer.
The airflow monitor ⁄ airflow sensor is used for monitoring or controlling airflows in ducts, at ventilators and dampers, for flow-dependent monitoring
of humidifiers and electric heating registers according to DIN 57100, part 420, or for use in connection with DDC systems.
TECHNICAL DATA
Power supply: 24 V AC ⁄ DC or
230 V AC +5 ⁄ -13 %, 50...60 Hz
Output: 1 or 2 potential-free relays (changeover contacts)
8 A, max. 2 kW or 0 - 10 V (relative, linearised on request)
Power consumption: approx. 3 VA
One-step:
Operating range: 0.1...30 m ⁄ s (adjustable)
Sensitivity: 0.1...30 m ⁄ s
Two-step (KLSW - 6):
Operating range: 0.1…15 m ⁄ s (adjustable)
Sensitivity: 0.1...5 m ⁄ s
Switching hysteresis: approx. 1…10 % (adjustable)
Start bridging: approx. 15...120 s (adjustable)
Switch-off delay: approx. 2 ...20 s (adjustable)
Max. sensor cable length: 50 m, avoid laying parallel with mains voltage-carrying lines,
or use shielded cables, minimum cross section 1.5 mm
2
per conductor, apply cable screen one-sided
Medium: pollutant-free, non-precipitating air
Ambient temperature: 0...+60 °C at the device; 0...+80 °C medium
Sensor: sensor breakage protection, temperature-compensated
Enclosure: plastic, material polyamide, 30% glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
KLSW-xx, KLGF -1 with display:
108 x 70 x 73.5 mm (Thor 2)
KLGF -1 without display:
72 x 64 x 37.8 mm (Tyr 1),
with quick-locking screws (slotted ⁄ Phillips head combination)
Cable gland: M 16 x 1.5; including strain relief, exchangeable, max. inner diameter 10.4 mm
Protective tube: metal (brass, nickel-plated), Ø 10 mm, nominal length NL = 140 mm
Process connection: by mounting flange (included in the scope of delivery)
Electrical connection: 0.14 - 1.5 mm
2
, via screw terminals on circuit board
Protection class: II (according to EN 60 730) at KLSW 3 (UB = 230 V AC)
III (according to EN 60 730) at UB = 24 V
Protection type: IP 65 (according to EN 60 529)
Standards: CE conformity, EMC directive 2014 ⁄ 30 ⁄ EU, low-voltage directive 2014 ⁄ 35 ⁄ EU
RHEASGARD
®
KLGF
– Duct airflow monitors
RHEASREG
®
KLSW
– Duct airflow monitors, one-step and two-step
Type ⁄ WG01 Relay
(Steps)
Power-
Supply
Output
Display Item No.
KLGF
KLGF 1 – 24 V AC ⁄ DC 0 -10 V (relative) 1701-3120-1000-000
KLGF 1_Display – 24 V AC ⁄ DC 0 -10 V (linearised) ■ on request
KLSW one-step
KLSW 3 1 230 V AC 1 x Changeover contact 1701-3011-0001-000
KLSW 4 1 24 V AC ⁄ DC 1 x Changeover contact 1701-3021-0000-000
KLSW two-step
KLSW 6 2 24 V AC ⁄ DC 2 x Changeover contact 1701-3022-0000-000
Note:
KLSW 6
is supplied as standard with a
manual reset button
!
Automatic reset
(without reset button)
on request