MAXIMUM PRESSURE: 250 PSI
INPUT VOLTAGE: 24 VAC, 60 HZ
SWITCH RATINGS: 5.8 FLA, 34.8 LRA
SWITCH CONTACTS: SPDT
ALARM CIRCUIT: 50 VA @ 24 VAC
Pilot Duty
FITTINGS
DIMENSIONS SPECIFICATIONS
Controls equipped with the EL1214-SV Probe can be mounted in standard reducing tees (supplied by others). Safgard manifolds, listed below, can be used
with all probe models.
MODEL PSI SIZE
FOEM-1 160 1 1/2" x 1 1/2" x 3/4"NPT
FOEM-2 160 1" x 1" x 3/4"NPT
FOEM-3 160 1 1/4" x 1 1/4" x 3/4"NPT
1214C-2 TEE 250 1" x 1" x 3/4"NPT
FOEM MANIFOLD
1214C-2 TEE
LIMITED MANUFACTURER’S WARRANTY
We warrant products manufactured by
Hydrolevel Company to be free from defects in
material and workmanship for a period of two
years from the date of manufacture or one year
from the date of installation, whichever occurs
first. In the event of any claim under this warran-
ty or otherwise with respect to our products
which is made within such period, we will, at our
option, repair or replace such products or refund
the purchase price paid to us by you for such
products. In no event shall Hydrolevel Company
be liable for any other loss or damage, whether
direct, indirect, incidental or consequential. This
warranty is your EXCLUSIVE remedy and shall be
IN PLACE OF any other warranty or guarantee,
express or implied, including, without limitation,
any warranty of MERCHANTABILITY or fitness
for a particular purpose. This warranty may not
be assigned or transferred and any unauthorized
transfer or assignment thereof shall be void and
of no force or effect.
5
9
/16
1
1
/16
5
1
/2
3
1
/16
BACK
3
7
/8
1
5
/8
1
1
/8
1
5
/8
2
3
/8
BOTTOM
126 Bailey Road
North Haven, CT 06473
Phone (203) 776-0473
FAX (203) 764-1711
www.hydrolevel.com
070218
MAINTENANCE: Remove and inspect probe annually. Clean any scale or build-up from the probe using a scouring pad or steel wool. Re-install the probe and
test the control operation in accordance with the Operating Instructions. If the probe is installed in an equalizing line of a steam boiler, the equalizing line
should be blown down weekly.
Test Pressure: 1000 PSI, All Models
PROBE DATA
2"
SQUARE
1
7
/8"
3
13
/16"
15
/16"
1"
3
/4" NPT
5
/16"
2"
SQUARE
1
1
/16"
3"
15
/16"
1"
3
/4" NPT
5
/16"
2"
SQUARE
1
7
/8"
4
9
/16"
1"
3
/4" NPT
5
/16"
1
11
/16"
EL1214 – STANDARD MODEL – 3/4" NPT
For 1/2", order Model EL1220
EL1214-SV – 3/4" NPT
For 1/2", order No. EL1220-SV
EL1214-P – 3/4" NPT
WARNING
Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages,
safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions
is recommended for unattended dwellings in climates subject to sustained below-freezing temperatures.