Chapter 4: Operation
Firmware – S2011 and S3012
Revision: 1 (9/98) 25 © Saftronics, Inc.
4.1 Operation Mode Selection
The FP5/GP5 has two operation modes, LOCAL and REMOTE, as described in Table 9. These two modes can be selected by
the Digital Operator LOCAL/REMOTE key only while the operation is stopped. The selected Operation mode can be verified by
observing the Digital Operator SEQ and REF LED’s as shown below. The Operation mode is set to REMOTE (run by control
circuit Terminals FV and FI frequency reference and RUN command from a control circuit terminal) prior to shipment. Multi-
function contact inputs from control circuit Terminals S3 to S6 are enabled in both Operation modes LOCAL/REMOTE.
LOCAL : Both frequency reference and RUN command are set by the Digital Operator. SEQ and REF LED’s go OFF.
REMOTE : Master frequency reference and RUN command can be selected as described in Table 9.
Table 9 Reference Selection in REMOTE Mode (n002: Operation Method Selection)
Setting Operation Method Selection
SEQ
LED
Reference Selection
REF
LED
0 Operation by RUN command from Digital Operator OFF Master frequency reference from Digital Operator OFF
1
Operation by RUN command from control circuit
terminal
ON Master frequency reference from Digital Operator OFF
2 Operation by RUN command from Digital Operator OFF
Master frequency reference from control circuit
Terminals FV and FI
ON
3
Operation by RUN command from control circuit
terminal
ON
Master frequency reference from control circuit
Terminals FV and FI
ON
4 Operation by RUN command from Digital Operator OFF
Master frequency reference set by serial
communication
ON
5
Operation by RUN command from control circuit
terminal
ON
Master frequency reference set by serial
communication
ON
6
Operation by RUN command from serial
communication
ON
Master frequency reference set by serial
communication
ON
7
Operation by RUN command from serial
communication
ON Master frequency reference from Digital Operator OFF
8
Operation by RUN command from serial
communication
ON
Master frequency reference from control circuit
Terminals FV and FI
ON