Datasheet
www.sbc-support.com
Features:
■
3-phase energy meter, 3 x 230/400 VAC 50 Hz
■
Direct measuring up to 65 A
■
Display of energy, power, voltage and current
■
Display of the total active power
■
M-Bus interface to retrieve the data
■
Reactive power per phase or total,
available via M-Bus interface
■
Up to 250 meters can be addressed
trough primary addresses
■
7-character display
■
Can be sealed with sealing cap (optional)
■
Accuracy class B according to EN50470-3,
accuracy class 1 according to IEC62053-21
Order number:
Standard Version: ALE3D5FM10C2A00
MID Version: ALE3D5FM10C3A00
Sealing Caps 4 104 7485 0
3-phase energy meters
with M-Bus interface
Energy meters with integrated M-Bus interface enable the
reading of all relevant data such as energy, current, voltage
and power (active and reactive).
Technical specications
Accuracy class B according to EN50470-3,
1 according to IEC62053-21
Operating voltage 3 × 230 / 400 VAC, 50 Hz
Tolerance –20 % / +15 %
Reference current
Maximum current
Iref = 10 A
Imax = 65 A
Starting current
Minimum current
Ist = 40 mA
Imin = 0.5 A
Power consumption Active 0.4 W per phase
Counting range 00˙000.00… 99˙999.99
100˙000.0… 999˙999.9
Display Backlit LCD, 6 mm high digits
Display without mains
voltage
Capacitor-aided LCD
Maximum 2 times during 10 days
Pulses per kWh LED: 1000 Imp./kWh
Assembly
Assembly On DIN rail 35 mm according to EN60715TH35
Connections
Main circuit
Wire size 1.5…16 mm², Pozidrive screwdriver size 1,
slotted screwdriver size 2, tightening torque 1.5…2 Nm
Connections
Control circuit
Wire size 2.5 mm², Pozidrive screwdriver size 0 or slot-
ted screwdriver size 2, tightening torque 0.8 Nm
Insulation properties 4 kV / 50 Hz test according to VDE0435 for energy
meters
6 kV 1.2 / 50 µs over voltage according to IEC 255-4
2 kV / 50 Hz according to VDE0435 for interface
Protection class II
Ambient temperature –25°…+55° C
Storage temperature –30°…+85° C
Environment Mechanical M2
Electromagnetic E2
Relative humidity 75 % without condensation
EMC/Immunity Surge voltage according to IEC61000-4-5:
on main circuit 4 kV on the M-Bus 1 kV
Burst voltage according to IEC61000-4-4:
on main circuit 4 kV on the M-Bus 1 kV
ESD according to IEC61000-4-2: Contact 8 kV, air 15 kV
Data sheet