TECHNICAL SALES GUIDE Capacity Range:60~1216KW T1/R410A/50Hz/60Hz C SERIES
Contents 2 3 3 6 9 10 11 14 15 16 18 20 21 1.MODELS LIST 2.NOMENCLATURE 3.FEATURES 4.PRODUCT DATA 5.PERFORMANCE CORRECTION 6.ANTIFREEZE 7.INSTALLATION 8.ELECTRICAL DATA 9.FIELD WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.WIRED CONTROLLER 12.ACCESSORIES 13.
Air-Cooled Scroll Chiller Technical Sales Guide 2 NOMENCLATURE QW F 80 G/Na C-H LS LS QW R FR80 MM G/Na C -F Model LS Water Chiller QW Scroll Compressor R Heat Pump F Air Cooled 80 3 Model Description Nominal Cooling Capacity M Module G Product number Na Refrigerant C Series number F Voltage Options Default- Cooling only R-Heat pump 65=60kW= 17 TR 80=76kW= 22 TR 130=120kW=34 TR 160=152kW=43 TR Na–R410A F 208~230V 3N~ 60Hz M 380~415V 3N~ 50Hz FEATURES 3.
3.2 Standard Specifications High Efficiency Full Load Operation Utilizing new scroll compressor technology, the chillers meet or exceed the performance requirements of ASHRAE 90.1. All system components are selected for optimum performance, including the condenser coil areas and evaporator sizes. Excellent Part Load Performance By using multi compressors on each chiller, unloading characteristics and part load performance are outstanding.
Air-Cooled Scroll Chiller Technical Sales Guide This well protected compressor includes a solid-state motor protection module, 4 individual motor winding sensors, a patented internal discharge temperature probe, and a patented shutdown feature that prevents reverse rotation. An internal discharge check valve helps prevent shutdown noise and comes standard with high and low pressure taps with Schrader valves, a sight glass, an oil level adjustment valve, and an off cycle crankcase heater.
3.4 Standard Control & Safety Devices The chiller's Unit Control Module is an innovative, modular microprocessor control design. It coordinates the actions of the chiller in an efficient manner and provides stand-alone operation of the unit. A Human Interface Panel is a standard component of the Chiller. Access to all unit controls is via the Human Interface Panel. Safety valve: Protects the unit against high discharge pressure.
Air-Cooled Scroll Chiller Technical Sales Guide 4.2 UNIT APPLICATION DATA Voltage Variation Min./Max. 342/420(50Hz) 198/242(60Hz) Ambient Air on Condenser coil Min./Max.℃(℉) -15/46 ( 41/115) 4.3 SPECIFICATION LSQWRF_MG/NaC-M LSQWF_MG/NaC-M Models Model 65 80 130 160 65 80 130 160 kW 60 76 120 152 60 76 120 152 kW 21.8 27.6 43.6 55.3 21.8 27.6 43.6 55.3 kW / / / / 65 80 130 160 Heating input power kW / / / / 21.7 26.7 43.3 53.
LSQWRF_MG/NaC-F LSQWF_MG/NaC-F Models Model 65 80 130 160 65 80 130 160 kW 60 76 120 152 60 76 120 152 kW 21.8 27.6 43.6 55.3 21.8 27.6 43.6 55.3 kW / / / / 65 80 130 160 Heating input power kW / / / / 21.7 26.7 43.3 53.
Air-Cooled Scroll Chiller Technical Sales Guide 5 PERFORMANCE CORRECTION Performance Correction Value Leaving Chilled Water ℃(℉) Ambient Temperature ℃(℉) 25(77) 30(86) 35(95) 5(41.0) 1.07 1.00 0.94 0.84 0.81 6(42.8) 1.10 1.03 0.97 0.87 0.83 7(44.6) 1.14 1.07 1.00 0.91 0.86 8(46.4) 1.17 1.10 1.03 0.94 0.88 9(48.2) 1.20 1.13 1.06 0.98 0.91 10(50.0) 1.23 1.16 1.09 1.01 0.93 11(51.8) 1.27 1.19 1.12 1.04 0.96 12(53.6) 1.31 1.23 1.15 1.07 0.99 13(55.4) 1.
6 ANTIFREEZE Ethylene Glycol Factors The units can operate with a leaving chilled fluid temperature from of20℉ to 60℉(-6℃ ~16℃) A glycol solution is required when leaving chilled fluid temperature is below4.5 ℃.The use of glycol will reduce the performance of the unit depending on concentration. % by Weight 10 20 30 40 50 Freezing Point ℃ ( ℉ ) -3.3(26) -7.8(18) -13.9(7) -21.7(-7) -33.3(-29) Ambient Temperature ℃ ( ℉ ) -16.7(2) -26.7(-16) 8.3(47) -1.7(29) -6.
Air-Cooled Scroll Chiller Technical Sales Guide INSTALLATION 7.1 Dimensions a、Graph for the shape and dimensions for LSQWRF65MG/NaC-M,LSQWF65MG/NaC-M,LSQWRF80MG/NaC-M, LSQWF80MG/NaC-M, LSQWRF65MG/NaC-F, LSQWF65MG/NaC-F ,LSQWRF80MG/NaC-F, LSQWF80MG/NaC-F 。 , 2155 2214 Rubber cushion aren t show in this view. b、Graph for the shape and dimensions for LSQWRF130MG/NaC-M,LSQWF130MG/NaC-M , LSQWRF160MG/NaC-M,LSQWF160MG/NaC-M, LSQWRF130MG/Na-F , LSQWF130MG/NaC-F , LSQWRF160MG/NaC-F,LSQWF160MG/NaC-F.
7.2 Rigging Instruction Caution Strict inspection and test have been made to every unit before it is delivered out of factories to ensure the performance and quality. Therefore, please be careful d u r i n g assembly and mobilization. Don’t damage control system and pipe components. Mobilize the unit to the nearest assembly location before removing the package. Keep the unit upward, carry the removed unit and assemble according to the following approach: a.
Air-Cooled Scroll Chiller Technical Sales Guide 7.
8 ELECTRICAL DATA Power cable specifications and air switch types in the following list are recommended for selection. Air switch capacity Unit Model 14 GREE Central Air Conditioners Min. sectional Min.
Air-Cooled Scroll Chiller Technical Sales Guide 9 FIELD WIRING DIAGRAM L1 L2 L3 N 9.1 FIELD WIRING DIAGRAM Q HL1 Q9 Q11 A2 XT3-11 QN A2 XT3-15 A2 XT3-13 M1 EH2 EH1 Q1 KM9 KM8 KM7 XT3-14 A1 A1 B1 C1 N XT3-12 A1 电压表 XT3-16 A1 Assistant Heater Q12 Q-Q11 3 KM9 KM7 KM8 KM7-KM9 Q12 HL1-4 Specification: HL2 HL4 1、Auxiliary electric heater is optional part for heat pump unit.The diagram connected shown above. 2、Cooling only type unit do not have AssistantHeater,KM7,KM8,HL4. 9.
COM1 CN2 9.3.
Air-Cooled Scroll Chiller Technical Sales Guide 6. System Safeties: Shall cause individual compressor systems to perform auto shut down. Manual reset required after the third trip of low pressure switch in 60 minutes. Manual reset required after every trip. Includes: high discharge temperature, high pressure switch. Compressor motor protector shall protect against damage due to high input current or thermal overload of windings. 7.
11 WIRED CONTROLLER 11.1 Operation View 1 Power XXXX-XX-XX XX:XX C Series Chiller 2 Cool【Heat/Defrost】 Run On【Off】 10 【Manual/Timer】 XModules【 【 3 Error On/off Reset 4 5 1.Power indicator(red): 6 7 Exit Confirm 8 9 the indicator is on when the wired controller is powered on, or otherwise it is off. 2.Run indicator(green): the indicator is on when the wired controller is started, or otherwise it is off.
Air-Cooled Scroll Chiller Technical Sales Guide 11.2 Menu Structure of Controller Menu Structure R Run Mode C Water Tin XX.X℃ C Water Tout XX .X℃ Startup H Water Tin XX.X℃ Auxiliary Heat H Water Tout XX .X℃ Auto-Antifreeze Defrost T1 XX.X℃ User’ s Setup User ’s Setu p Timer Setup Defrost T2 XX.X℃ Clock Setup Anti-Heat T XX.X℃ Ambient T XX .X℃ Sound Suction T1 XX.X℃ Backlight Suction T2 XX.X℃ ECO. Model Exhaust T1 XX.X℃ Memory Start Temp. View Quiet Model Exhaust T2 XX.X℃ Throttle T1 XX.
12 ACCESSORIES S=Standard O=Optional F=Field supply Model 20 GREE Central Air Conditioners Accessories Name Cooling only Heat pump 1 Module unit S S 2 wired controller (necessary) O O 3 Four-core control connection cord (3 meters) S S 4 Three-core signal cable (3 meters) F F 5 Water flow switch S S 6 Electric control box F F 7 Auxiliary electric heater ---- O 8 Power connection wire F F 9 Control connection cord F F 10 Flexible joint F F 11 Thermometer F F 1
Air-Cooled Scroll Chiller Technical Sales Guide 13 APPLICATION DATA Unit Location The chillers are designed for outdoor installation. When selecting a site for installation, be guided by the following conditions: 1. For outdoor locations of the unit, select a place having an adequate supply of fresh air for the condenser. 2. Avoid locations beneath windows or between structures where normal operating sounds may be objectionable. 3. Installation sites may be either on a roof, or on the ground. 4.
Cooler Flow Range: Chiller ratings and performance data pertain to cooling temperature rise of 10 ℉ (12.4℃ ). Chillers maybe suitable for operation in a range from 5.4 to 14.5 ℉ (-15~-9.9 ℃ )temperature rise without adjustment, provided flow limits are not exceeded. High flow rate is limited by pressure drop that can be tolerated ( for any high flow rate value larger than values in performance tables, please refer to GREE factory).