3.9 SIZING OF AC OUTPUT WIRING AND BREAKERS
3.9.1 EVO-1212F and EVO-1224F
120 VAC output is supplied through NEMA5-15 Duplex GFCI Outlets (15, Fig 2.1). The outlets
are protected against over current through 15A Circuit Breaker (14, Fig 2.1).
Use power cord with NEMA5-15 plug and conductor size AWG #14.
3.9.2 EVO-1212F-HW and EVO-1224F-HW
WARNING!
For EVO-1212F-HW and EVO-1224F-HW, AC Breakers for the AC output circuits have
NOT been provided internally. These have to be provided externally by the installer
/ user based on guidelines given below. Please note that guidelines given below on
wire sizing and over-current protection will be superseded by the applicable National
/ Local Electrical Codes.
MISE EN GARDE!
Pour EVO-1212F-HW and EVO-1224F-HW breakers AC pour les circuits d’entrée AC ont pas été fournis en
interne. Ceux-ci doivent être fournies à l’extérieur par l’installateur / utilisateur sur la base des directives don-
nées ci-dessous. Se il vous plaît noter que les directives ci-dessous sur dimensionnement des câbles et protec-
tion contre les surintensités seront remplacées par les nationaux / codes électriques locaux applicables.
Table 3.3 provides details of wire and breaker sizing for the AC output side for EVO-1212F-
HW and EVO-1224F-HW.
AC wiring and breaker sizes on the AC output side are required to be determined by the
Rated Load Current when operating in Inverter Mode (Column 1).
Table 3.3 SIZING OF AC OUTPUT WIRING AND BREAKERS
Model No.
(Rated Output
Power in In-
verter Mode )
(Column 1)
Rated AC Out-
put Current in
Inverter Mode
(See Note 1)
(Column 2)
NEC Ampacity
= 125% of
Column 2
(See Note 2)
(Column 3)
Conductor Size
based on NEC
Ampacity at
Column 3
(See Note 3)
(Column 4)
Size of Breaker
(Column 5)
EVO-1212F-HW
(1200VA)
10A 12.5A AWG #14
External Breaker
15A
EVO-1224F-HW
(1200VA)
10A 12.5A AWG #14
External Breaker
15A