54 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 55
3.14.2.2 EVO-1212F-HW and EVO-1224F-HW: AC Side Grounding of Typical
Shore Based Installation
Refer to the Installation Diagram for Typical Shore Based Installation for EVO-1212F-HW and
EVO-1224F-HW at Fig 3.13
(a)
AC Input Gr
ounding: The metal chassis of EVO
TM
gets bonded to the Grounding Electrode
(GE) / “Ground Rod” of the premises as follows:
The metal chassis of EVO
TM
is connected to the “INPUT GND” Terminal (23) of the AC
Input / Output Terminal Block (20) in EVO
TM
The “INPUT GND” T
erminal (23) of the AC Input / Output Terminal Block (20) in EVO
TM
gets connected to the Grounding Bus Bar (G-B) in the Grid Electrical Panel through the
grounding wire of AC input connection
The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground
through the Grounding Electrode (GE) / “Ground Rod” of the premises
(b)
AC Output Gr
ounding: The metal chassis of the AC load(s) gets connected to the
Grounding Electrode (GE) / “Ground Rod” of the premises as follows:
The metal chassis of the AC load(s) is connected to the Gr
ounding Bus Bar (G-B) of the
Electrical Sub Panel for EVO
TM
Output
Gr
ounding Bus Bar (G-B) of the Electrical Sub Panel for EVO
TM
Output is connected to
metal chassis of EVO
TM
through the “OUTPUT GND” Terminal (26) of the AC Input /
Output Terminal Block (20) in EVO
TM
.
The metal chassis of EVO
TM
is connected to the “INPUT GND” Terminal (23) of the AC
Input / Output Terminal Block (20) in EVO
TM
The “INPUT GND” T
erminal (23) of the AC Input / Output Terminal Block (20) in EVO
TM
gets connected to the Grounding Bus Bar (G-B) in the Grid Electrical Panel through the
grounding wire of AC input connection
The Gr
ounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground
through the Grounding Electrode (GE) / “Ground Rod” of the premises
3.14.3 AC Side Grounding of Typical RV / Mobile Installation
3.14.3.1 EVO-1212F and EVO-1224F: AC Side Grounding of Typical
RV / Mobile Installation
Refer to the Installation Diagram for Typical RV / Mobile Installation for EVO-1212F and EVO-
1224F at Fig 3.14.
(a) AC Input Grounding: The metal chassis of EVO
TM
gets bonded to (i) the RV / Vehicle
Chassis Ground when not connected to Grid Power and (ii) to the Grounding Electrode
(GE) / Ground Rod of the Grid Power System of the premises when connected to Grid
Power through the Grid Power Supply Cord as follows:
The metal chassis of EVO
TM
is connected to the Grounding Pin (G) of the AC Power Inlet
Plug (9)
The Grounding Pin (G) of the AC Power Inlet Plug (9) gets connected to the Grounding
Bus Bar (G-B) in the Electrical Panel of the RV / vehicle through the grounding wire of
AC input connection.
SECTION 3 | Installation