Product Manual

56 | SAMLEX AMERICA INC.
The Grounding Bus Bar (G-B) in the Electrical Panel of the RV / vehicle is bonded to the
RV / Vehicle Chassis Ground. When the RV / vehicle is connected to the Grid through
the Grid Power Inlet and Cord, the RV / Vehicle Chassis Ground gets bonded to the
Earth Ground of the premises through the Grounding Electrode (GE) / “Ground Rod” of
the premises of the Grid Power System supplying the RV / Vehicle .
(b)
AC Output Gr
ounding: The metal chassis of AC load(s) gets bonded to (i) the RV /
Vehicle Chassis Ground when not connected to Grid Power and (ii) to the Grounding
Electrode (GE) / Ground Rod of the Grid Power System of the premises when connected to
Grid Power through the Grid Power Supply Cord as follows:
The metal chassis of the AC load(s) is connected to the Grounding socket (G) of the
GFCI outlet (10) in EVO
TM
through the Grounding Conductor of the load connection
Gr
ounding socket (G) of GFCI outlet “10” in EVO
TM
is connected to the metal chassis of EVO
TM
.
The metal chassis of EVO
TM
is connected to the Grounding Pin (G) of the AC Power Inlet
Plug (9)
The gr
ounding Pin (G) of the AC Power Inlet (9) gets connected to the Grounding Bus
Bar (G-B) in the Electrical Panel of the RV / vehicle through the grounding wire of AC
input connection.
The Gr
ounding Bus Bar (G-B) in the Electrical Panel of the RV / vehicle is bonded to the
RV / Vehicle Chassis Ground. When the RV / vehicle is connected to the Grid through
the Grid Power Inlet and Cord, the RV / Vehicle Chassis Ground gets bonded to the
Earth Ground of the premises through the Grounding Electrode (GE) / “Ground Rod” of
the premises of the Grid Power System supplying the RV / Vehicle
3.14.3.2 EVO-1212F-HW and EVO-1224F-HW:
Refer to the Installation Diagram for Typical RV / Mobile Installation for EVO-1212F-HW and
EVO-1224F-HW at Fig 3.15.
(a) AC Input Grounding: The metal chassis of EVO
TM
gets bonded to (i) the RV / Vehicle
Chassis Ground when not connected to Grid Power and (ii) to the Grounding Electrode
(GE) / Ground Rod of the Grid Power System of the premises when connected to Grid
Power through the Grid Power Supply Cord as follows:
The metal chassis of EVO
TM
is connected to the “INPUT GND” Terminal (23) of the AC
Input / Output Terminal Block (20) in EVO
TM
The “INPUT GND” Terminal (23) of the AC Input / Output Terminal Block (20) in
EVO
TM
gets connected to the Grounding Bus Bar (G-B) in the Electrical Panel of the RV
through the grounding wire of AC input connection
The Gr
ounding Bus Bar (G-B) in the Electrical Panel of the RV / vehicle is bonded to the
RV / Vehicle Chassis Ground. When the RV / vehicle is connected to the Grid through
the Grid Power Inlet and Cord, the RV / Vehicle Chassis Ground gets bonded to the
Earth Ground of the premises through the Grounding Electrode (GE) / “Ground Rod” of
the premises of the Grid Power System supplying the RV / Vehicle
(b) AC Output Grounding: The metal chassis of the AC load(s) gets bonded to (i) the RV
/ Vehicle Chassis Ground when not connected to Grid Power and (ii) to the Grounding
Electrode (GE) / Ground Rod of the Grid Power System of the premises when connected to
Grid Power through the Grid Power Supply Cord as follows:
SECTION 3 | Installation