Product Manual
84 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 85
TABLE 5.2 BATTERY CHARGER SECTION – CHARGING PROFILE OPTIONS AND CHARGING
STAGES (CONTINUED)
Options under
Parameter
"CHARGING PROFILE"
Charging Stages
Battery Type and battery
loading condition
1 = 3 Stage Type 1 1. Bulk Stage: Charge at constant current
equal to programmable parameter
“BULK CURRENT”
• Transition to Absorption Stage when
voltage rises to programmable param-
eter “ABSORP VOLTAGE”.
2. Absorption Stage: Charge at constant
voltage at programmable parameter
“ABSORP VOLTAGE”.
• Time in Absorption Stage is program-
mable through parameter “ABSORP
TIME”. Transition to Float Stage there-
after
3.
Float Stage:
Charge at constant voltage
equal to programmable parameter
“FLOAT VOLTAGE”
•
Reset to Bulk Stage under the follow
-
ing conditions:
-
After 10 days in Float Stage, or
-
V
oltage drops to programmable volt-
age parameter “RESET TO BULK”
- Lead Acid: Flooded and sealed
– AGM/Gel Cell
- Lithium (See Section 5.6)
2 = 3 Stage Type 2 1.
Bulk Stage: Charge at constant current
equal to programmable parameter
“BULK CURRENT”
•
T
ransition to Absorption Stage when
voltage rises to programmable param-
eter “ABSORP VOLTAGE”.
2.
Absorption Stage:
Charge at constant
voltage at programmable parameter
“ABSORP VOLTAGE”.
•
T
ransition from Absorption to Float
when current drops to programmable
parameter “ABSORP EXIT AMPS”
3. Float Stage: Charge at constant voltage
equal to programmable parameter
“FLOAT VOLTAGE”
•
Reset to Bulk Stage under the follow
-
ing conditions:
-
After 10 days in Float Stage, or
-
V
oltage drops to programmable volt-
age parameter “RESET TO BULK”
-
Lead Acid: Flooded and
Sealed – AGM/Gel Cell
- Lithium (See Section 5.6)
SECTION 5 | Battery Charging in Evolution
TM
Series