APPENDIX A
Battery over voltage!
EVO Inverter Charger is in FAULT MODE because the battery voltage has risen to the
set upper threshold of “BATT OVER VOLTAGE”
(a) AC input is not available and EVO Inverter Charger is operating in
Inverting Mode:
There will be no AC output because the Inverter Section will be switched OFF.
The Green LED marked “Status” will be switched OFF and the Red LED marked
“Fault” will be steady ON. The buzzer in EVO Inverter Charger will beep steady
The fault will be cleared automatically when the battery voltage drops to 0.5V
below the set upper threshold of “BATT OVER VOLT”
(b) AC input is available and EVO Inverter Charger is operating in Charging Mode:
There will be no AC output or charging because the Transfer Relay will be de-
energized and PWM drive to the Inverter Section will be switched OFF.
The fault will be cleared automatically when the battery voltage drops to 0.5V
below to the set upper threshold of “BATT OVER VOLT”. The EVO Inverter
Charger will restart in Inverting Mode, synchronize with the AC input and then,
the Transfer Relay will be energized to transfer to AC input at zero crossing. The
unit will, thus, resume operation in “Charging Mode”
Input over current!
EVO Inverter Charger is in FAULT MODE because the input current being drawn from the
AC input source (Input current = Charging Current + Pass Through Current to the load) is
1A more than the set threshold of “ MAXIMUM CURRENT” for 5 seconds
There will be no AC output because the Transfer Relay will be de-energized, charging
will be stopped and PWM drive to the Inverter Section will be switched OFF. The
Green LED marked “Status” will be switched OFF and the Red LED marked “Fault”
will be steady ON. The buzzer in EVO Inverter Charger will beep steady
EVO Inverter Charger will be latched in OFF condition and will require
manual reset by powering OFF, waiting for 1 minute and then powering ON
again
The set threshold of “MAXIMUM CURRENT” (Section 4.5) should match the breaker
capacity of the AC input source / AC input Branch Circuit. If AC input current
capacity cannot be increased, reduce the AC load / “BULK CURRENT” (Section 4.4)
accordingly.
Output over current!
EVO Inverter Charger is in FAULT MODE because the instantaneous output current
being drawn by the AC load in Inverting Mode is 330% of the rated value of the
EVO Inverter Charger (sampling time is 33 micro seconds)
There will be no AC output because the Inverter Section will be switched OFF.
The Green LED marked “Status” will be switched OFF and the Red LED marked
“Fault” will be steady ON. The buzzer in EVO Inverter Charger will beep steady
EVO Inverter Charger will be latched in OFF condition and will require
manual reset by powering OFF, waiting for 1 minute and then powering
ON again
Ensure that the maximum instantaneous surge current of the load is not more
than 300% of the rated current of the EVO Inverter Charger for 1 millisecond
EVO Inverter Charger is in FAULT MODE because of overload conditions in Inverting
Mode:
There will be no AC output because the Inverter Section will be switched OFF.
The Green LED marked “Status” will be switched OFF and the Red LED marked
“Fault” will be steady ON. The buzzer in EVO Inverter Charger will beep steady
EVO Inverter Charger will be latched in OFF condition and will require manual
reset by powering OFF, waiting for 1 minute and then powering ON again
Ensure that overloading is limited to the specied limit
Output over load! Output voltage is less than 96Vrms for 300 cycles (5 seconds at 60Hz)
Output over load 1! Output power is over the Power Boost Rating (110%) for 30 min
Output over load 2! Output power is over the Power Boost Rating (120%) for 5 minutes
Output over load 3! Output power is over the Power Boost Rating (140%) for 30 seconds
Output over load 4! Output power is over the Power Boost Rating (150%) for 5 seconds
SECTION 7 | Fault Messages and