Manual
26 | SAMLEX AMERICA INC.
for a 12V inverter is given below:
Let us say that the total AC Watts delivered by the 12V inverter = 1000W.
Next, the energy required by the load in Ampere Hours (Ah) is determined.
Now, the capacity of the batteries is determined based on the run time and
the usable capacity.
And nally, the actual desired rated capacity of the batteries is determined based on
the fact that normally only 80% of the capacity will be available with respect to the
rated capacity due to non availability of ideal and optimum operating and charging
It will be seen from the above that the nal rated capacity of the batteries is almost 2
Thus, as a rule of thumb, the Ah capacity
of the batteries should be twice the energy required by the load in Ah.
SECTION 7 | General Information on Batteries for
Powering Inverters