Connecting Ground Cable
To connect Ground Cable
1 Make sure you have the following items:
Table 26. Parts and Tools for connecting Ground Cable
Category
Description
Installation Section
MGB ~ RRU Ground Terminal
Cable
AWG 8 × 1C
Heat Shrink Tube
(Spec/Color/Length)
Ф 0.47 in. (12mm)/Clear/1.96 in. (50 mm)
Pressure Terminal
MGB
Checking MGB specifications per site and preparing connecting parts
RRU
AWG 8, 2 Hole, Hole diameter :1/4 in.( 6.4 mm),
Hole spacing : 0.63 in.(16 mm)
Fastener
MGB
Checking MGB specifications per site and preparing connecting parts
RRU
M6 × 14L SEMS(Hex. +) / 2 EA
Recommended
Torque Value
M6 SEMS
43 lbf·in(50 kgf·cm)
Working Tools
Cable Cutter, Wire Stripper, Crimping tool, Heating Gun, Nipper, Screw Driver (‘+’, No.
3), Torque Driver (20~90 lbf·in.), Screw Driver Bit (‘+’, No. 3)
For the pressure terminal or the cable, the UL Listed products or equivalent should
be used.
Ex) Manufacturer-Panduit
RRU : AWG8 Pressure Terminal (LCD8-14A-L)