User's Manual
Mobile WiMAX Indoor RAS SPI-2210 System Description/Ed.07
© SAMSUNG Electronics Co., Ltd. 2-16
Environmental Condition
The table below lists the environmental conditions and related standards such as
operational temperature and humidity.
Category Range Applied Standard
Temperature Condition
a)
0~50°C (32~122°F) -
Humidity Condition
a)
5~95%
However, the vapor content for air
of 1 kg should not exceed 0.024 kg.
GR-487-CORE Sec.3.34.2
Altitude -60~1,800 m (-197~6,000 ft) GR-63-CORE Sec.4.1.3
Earthquake Zone 4 GR-63-CORE Sec.4.4.1
Vibration Commercial Transportation Curve 2 GR-63-CORE Sec.4.4.4
Noise (sound pressure level) Under 65 dBA in height of 1.5 m
and distance of 0.6 m.
GR-63-CORE
(Issue 2, April, 2002)
Sec.4.6
Electromagnetic Wave (EMI) Standard satisfied FCC Title47 Part 15 Class A
GR-1089-CORE Sec. 3.2
US Federal Regulation Standard satisfied FCC Title47 Part27
a) The standards of temperature/humidity conditions are based on the value on the position where is 400 mm
(15.8 in) away from the front of the system and in the height of 1.5 m (59 in) on the bottom.
Environmental Alarm
The table below lists the environmental alarm provided in the indoor SPI-2210 in default.
Category Description
Fan controller (FCM) Status Fan controller (FCM) Fail Report
Temperature Alarm
High Temperature
Fan Fail - Digital Main Block (DMB) Fan Fail
- RF Block (RFB) Fan Fail
GPSR Specification
The table below lists the GPS Receiver (GPSR) characteristics of indoor SPI-2210.
Category Description
Received Signal from GPS 1PPS, ToD
Reference signal 8 kHz
Accuracy/Stability 0.01 ppm