User's Manual

Table Of Contents
Samsung CDMA BSS: Indoor BTS Installation Manual
17
BSS Version 4, Document V4D0001 release 0.5, Indoor BTS Installation
Manual, release 2.0
Isolation testing
The following isolation test should be done on the SBR1 rack to
verify proper frame grounding insulation:
1 Connect the negative lead of the DVM to the anchor bolt, and
connect the positive lead to an unpainted surface within the rack, as
shown in the following figure:
2 Measure the isolation resistance.
3 The isolation resistance should be higher than 20M ohms (infinite)
when it is tested by the DVM.
4 If the isolation measurement result shows a value less than 20M
ohms, repair or adjust the anchor bolts, fiber mounting spacer, and
rack position.