User Manual

CHAPTER 2. Installation
2-60 © SAMSUNG Electronics Co., Ltd.
Figure 2.44 Driven Rod Construction
2.5.1.2 San Earth Typical Installation
1) Remove dust completely and wash the target area.
2) Install a bear copper wire. Fix the bear copper wire with a concrete nail.
3) Mix a 25 kg bag of san earth with 10 L of water to cover the bear copper wire 30 cm in
width and 3 cm in thickness.
4) The earth cable and the bear copper wire will be connected to an earth terminal board
in a building through cad welding.
5) Connect the earth cable connected to the bear copper wire to the earth terminal board.
Figure 2.45 San Earth Typical Installation
Earth cable
CAD Welding
Hot Melt
Adhesion
Bear coppe
r
wire
Earth rod
San Earth
Earth cable
MGB connection
CAD Welding
Hot Melt
Adhesion
삭제됨: 1