User Manual

CHAPTER 2. Installation
2-66 © SAMSUNG Electronics Co., Ltd.
2.5.2.4 Antenna Feeder Cable Grounding
The antenna feeder cable should be earthed by using the ground kit under the copper
plate(TGB, Tower Ground Bar) installed within the lower part of the iron tower or the
antenna feeder cable duct.
Figure 2.51 Antenna Feeder Cable Grounding
The procedure for performing the grounding of the antenna feeder cable is as follows:
1) Remove the covering of the 7/8 inch feeder about by 15 mm.
2) Connect the ground kit to the feeder, and lift up to where the covering of the feeder is
stripped off.
3) Wrap the cable of the ground kit about by 7~10 cm with the vinyl tape, and wrap the
cable by using the insulation tape again.
4) Fix the driven rod(GND BAR) in the ground kit and the iron tower copper rod by
using the copper bolt.
The TGB location and the method of connecting to the iron tower grounding cable are as
follows:
Table 2.1 TGB Location and Method of Connecting to Iron Tower Grounding Cable
Item Description
TGB location Bottom of feeder line port or tower/Top of tower
Material Pure copper
Installing method Separate from the iron tower electrically by using insulator.
Installing method Draw the GV 38 mm
2
grounding cable(AWG 4) towards the surface, and
weld to the iron tower grounding cable.
Ground Kit
7/8” Feeder Line
30
15
TGB
(Tower Ground Bar)
TGB Grounding Cable
삭제됨: 1