Specifications

139
B
UILDING
M
ANAGEMENT
S
YSTEM
(3) Analog output property
Property identifier Property data
Check
code
Support
DMS2
1 Object identifier BACnetObjectIdentifier R V
2 Object name CharaterString R V
3 Object type BACnetObjectType R V DEVICE
4 Present value REAL W V
5 Description CharacterString O V
AI_Instance_device
address
6 Device type CharacterString O
7 Status Flags BACnetStatusFlags R V
Communication
Status_Flags FAULT flag
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V
General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
9 Reliability BACnetReliability O V
10 Out of service BOOLEAN R V
Communication error
TRUE
11 Units BACnetEngineeringUnits R V
12 Min pres value REAL O V
13 Max Pres Value REAL O V
14 Resolution REAL O
15 Priority array BACnetPriorityArray R V
16 Relinquish default REAL R V
17 COV increment REAL
O
(1)
18 Time Delay Unsigned
O
(2)
19 Notification class Unsigned
O
(2)
20 High limit REAL
O
(2)
21 Low limit REAL
O
(2)
22 Deadband REAL
O
(2)
23 Limit enable BACnetLimitEnable
O
(2)
24 Event Enable BACnetEventTransitionBits
O
(2)
25 Acked transition BACnetEventTransitionBits
O
(2)
25 Notify type BACnetNotifyType
O
(2)